4. Configuration
71
Internal-> IEC 60870-5-104 Digital
Internal Quality
IEC 60870-5-104 Quality
Flags
VALIDITY
FLAG_RESTART
ANY
NOT TOPICAL
FLAG_COMM_FAIL
ANY
NOT TOPICAL
FLAG_REMOTE_SUBSTITUTED
ANY
SUBSTITUTED
FLAG_LOCAL_SUBSTITUTED
ANY
SUBSTITUTED
FLAG_FILTER
ANY
-
FLAG_OVERFLOW
ANY
-
FLAG_REFERENCE_ERROR
ANY
-
FLAG_INCONSISTENT
ANY
-
FLAG_OUT_OF_RANGE
ANY
-
FLAG_INACCURATE
ANY
-
FLAG_OLD_DATA
ANY
NOT TOPICAL
FLAG_FAILURE
ANY
INVALID
FLAG_OPERATOR_BLOCKED
ANY
BLOCKED
FLAG_TEST
ANY
-
ANY
VALIDITY_INVALID
INVALID
Tabela 4-10. Internal Conversion to IEC 60870-5-104 to Digital Points
Internal->IEC 60870-5-104 Analogic
Internal Quality
IEC 60870-5-104 Quality
Flags
VALIDITY
FLAG_RESTART
ANY
NOT TOPICAL
FLAG_COMM_FAIL
ANY
NOT TOPICAL
FLAG_REMOTE_SUBSTITUTED
ANY
SUBSTITUTED
FLAG_LOCAL_SUBSTITUTED
ANY
SUBSTITUTED
FLAG_FILTER
ANY
-
FLAG_OVERFLOW
ANY
OVERFLOW
FLAG_REFERENCE_ERROR
ANY
INVALID
FLAG_INCONSISTENT
ANY
INVALID
FLAG_OUT_OF_RANGE
ANY
OVERFLOW
FLAG_INACCURATE
ANY
INVALID
FLAG_OLD_DATA
ANY
NOT TOPICAL
FLAG_FAILURE
ANY
INVALID
FLAG_OPERATOR_BLOCKED
ANY
BLOCKED
FLAG_TEST
ANY
-
ANY
VALIDITY_INVALID
INVALID
Tabela 4-11. Internal Conversion to IEC 60870-5-104 to Analogic Points