2. Technical Description
15
Electronic Tag on Display (ETD)
Yes
Isolation
Logic to protective earth
2500 Vac / 1 minute
Logic to Ethernet interfaces
1500 Vac / 1 minute
Logic to serial port (COM 2)
2000 Vac / 1 minute
Logic to IRIG-B port
2500 Vac / 1 minute
Ethernet interfaces to protective
earth
1500 Vac / 1 minute
Ethernet Interface to serial port
(COM 2)
2500 Vac / 1 minute
Ethernet Interface to Ethernet
Interface
1500 Vac / 1 minute
Serial Port (COM 2) to protective
earth
2500 Vac / 1 minute
Current consumption from backplane
rack
1500 mA
Dissipation
7.5 W
Operation temperature
-5 to 60 °C
Storage temperature
-25 to 85 °C
Operating and storage relative
humidity
5 to 96 %, no condensation.
Conformal coating
Yes
Protection Level
IP 20
Standards
IEC 61131-2
IEC 61131-3
IEC 61850
CE, Electromagnetic Compatibility (EMC) and Low-Voltage
Directive (LVD).
RoHS directive
Module dimensions (L x A x P)
38.0 x 235.3 x 184.2 mm
Package dimensions (L x A x P)
55.0 x 308.0 x 266.0 mm
Weight
1000 g
Weight with package
1300 g
Table 2-2. Main Features
Notes:
Types of tasks:
Task is an object used to call POUs. A Task can be triggered by period, events or
can run in freewheeling mode. Each task can call one or more POUs.
Real Time Clock (RTC):
The retention time, which is the time that the real time clock keeps
updating the date and time after the CPU goes off, is 15 days considering environments with
temperature of 25 °C. Up to the maximum product operation temperature, retain time is reduced to 10
days.
One Touch Diag (OTD):
This option is available to the user only when the module is in operational
mode.
Isolation:
Logic is the name for the internal circuits such as processors, memories and interfaces
with backplane rack.
Conformal coating:
Conformal coating protects the electronic components inside the product from
humidity, dust and other harsh elements to electronic circuits.