37
Now, each time the "
key
" button is pressed, the E-lock is released for the pre-set
time. Use the "#" button to turn the function off.
Upon entering the program, the current value of the E-lock set time and delay is
displayed (default setting is "
04
" - 0s delay and 4s of E-lock time). While the
current value is displayed, enter a new value and confirm with the "
key
" button or
press the "#" button to exit the program without saving changes. Only three-digit
number
XXY
, (such as 254) can be used in the program, where the first two digits
(max 25) define the E-lock delay time multiplied by 10
(XX
x 10s. = 250s) and the
third digit defines the E-lock time in seconds (
Y
= 4s).
For example, to set the E-lock time to 6s, enter 6 and confirm with the
"key"
button (0 sets time to 10s)
.
By entering only one digit
(Y
) no delay is set.
Entering 125 will set the E-lock time to 5s and the delay time to 12x10s = 120s.
Entering 80 will set the E-lock time to 10s and the delay time to 8x10s = 80s.
The delay time can be used:
- in slave units as a delay time for the further door opening function.
This is the time during which pressing the "key" button on the slave unit the E-
lock released. This delay is activated when the E-lock is activated in the master
unit (the master unit sends a "further door opening" pulse to a downstream
unit).
The delay time is indicated by the key symbol appearing on the display and
the set delay time, counting down to zero. If the key button is pressed during
this countdown, the E-lock is immediately engaged. Pressing the "
#
" button will
end the countdown without releasing the E-lock.
If no key is pressed, the unit will terminate the countdown after the pre-set
delay time by returning to the stand-by mode or, with bit 1 enabled in P16, it
will engage the E-lock.
For correct operation of the further door opening function in the bit 4 in P16
must be enabled in the master unit.
- in master units, as the E-lock release delay after the terminals of the additional
INPUT are closed. In order to automatically engage the E-lock after the end of
the countdown, bit1 must be enabled in P16. If the delay is not set, the E-lock
will be engaged immediately after the terminals of the additional INPUT are
closed.