- 53 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.4~3
4.3.4 Parameter - Details in alphabetical order (continued)
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Contr
ol
system
(digital
value if
dif
fer
ent)
Contr
ol
Panel
Control
function
12
Accessible via control system or Control Panel (menu point: co.Fu)!
Transparent
(1)
c.trA
Control function Transparent (= default)
:
Direct access to DIs / DOs via fi eldbus
Overload
relay
(2)
c.oVL
Control function Overload relay
:
Similar to overload relay.
Attention!
Normal signal on output DO0 is on and the connected contactor starts the
motor.
Direct starter
(3)
c.dir
Control function Direct starter
:
Direct start of a motor for one direction of rotation
Reversing
starter
(4)
c.reV
Control function Reversing starter
:
Reverse start of a motor for two direction of rotation
Star-delta
starter 1
(5)
c.Sd1
Control function Star-delta starter 1
:
Star-delta start via 2 DOs
Pole-chan-
ging starter 1
(6)
c.Pch
Control function Pole-changing starter 1
:
Pole-changing start for two-pole and dahlander motors
Actuator 1
(7)
c.Ac1
Control function Actuator 1
:
OPEN and CLOSE Position via limit switch
Actuator 2
(8)
c.Ac2
Control function Actuator 2
:
OPEN and CLOSE Position via limit and torque switch
Actuator 3
(9)
c.Ac3
Control function Actuator 3
:
OPEN Position via limit switch, CLOSE Position via limit and torque switch
Actuator 4
(10)
c.Ac4
Control function Actuator 4
:
OPEN Position via limit and torque switch, CLOSE Position via limit switch
Star-delta
starter 2
(11)
c.Sd2
Control function Star-delta starter 2
:
Star-delta start via 3 DOs
Cooling time
10
Accessible via control system or Control Panel (menu point: ti.co)!
Cooling time simulates the cooling behaviour of the inoperating motor after tripping.
Remark:
During cooling time is running, RUN commands are not accepted. WARNING is monitored.
30-3600 s
(300-36000)
0030-
3600
30-3600 s
Steps via control system: 0.1 s: 30 s = 0,1 s x 300
Steps via Control Panel: 1 s: 30 s = 1 s x 30
Default value: 1200 resp. 0120 (=120 s)