UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.4~15
4.3.4 Parameter - Details in alphabetical order (continued)
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Contr
ol
system
(digital
value if
dif
fer
ent)
Contr
ol
Panel
Reset to de-
fault
Accessible via Control Panel (menu point: rESE) only!
Sets all parameter values to default values exept the parameters address, number of starts, number
of trips and operating hours.
Reverse
lock-out time
17
Accessible via control system or Control Panel (menu point: ti.rL)!
Only for bidirectional starters!
Time starts running with the OFF command. An Off command is nessesary between run forward
and reverse, that means between RUN FORWARD and RUN REVERSE command.
A RUN command into the other direction will be acepted only when the reverse lock-out time has
elapsed.
2-36000
0002-
3600
0.2-3600 s
- Adjustment via control system: step: 0.1 s: 0.2 s = 0.1 s x 2
- Adjustment via Control Panel: step: 1 s: 2 s = 1 s x 2
A "0" set with the Control Panel corresponds to 0.2 s.
Default value: 20 resp. 0002 (= 2 s)
Self test
Accessible via Control Panel (menu point SELF): Start self test with [ENTER]: The text "buSY" on
the Control Panel shows the correct test run. Self test is OK if no fault signal is set after the test.
Accessible via bus command bit "Self Test": Start self test with 0-1 edge. Self test is OK if no
fault signal is set after the test.