- 61 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.4~11
4.3.4 Parameter - Details in alphabetical order (continued)
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Contr
ol
system
(digital
value if
dif
fer
ent)
Contr
ol
Panel
Emergency by
PLC
27
Accessible via control system only!
Details see chapter 3.4.3.
Off
(0)
-
Emergency start by PLC locked (= default)
:
The UMC22 does not accept the command PREPARE EMERGENCY
START from control station.
On
(1)
-
Emergency start by PLC possible
:
The UMC22 accepts the command PREPARE EMERGENCY START from
control station.
Fault output
24
Accessible via control system or Control Panel (menu point: F.out)!
Off
(0)
Fo.of
Fault output not activated (= default):
Output DO2 is free available..
On
(1)
Fo.on
Fault output activated / light steady
Output DO2 is used for fault indication.
blink
(3)
Fo.bl
Fault output activated /fl ashing
Output DO2 is used for fault indication.
High current
threshold
09
Accessible via control system only!
100-800 %
(20-160)
-
100-800 % x Set current
(step: 5 %): 100 % = 5 % x 20
Warning when motor current is above threshold after start-up time has
elapsed.
Default value: 30 (= 150 %)
Local control
22
Accessible via control system or Control Panel (menu point: L.ctr)!
Local control is possible on various ways:
-
Local operation via digital inputs
- adjustable via
Local control
-
Direct panel control
for simplifi ed operation with the Control Panel - adjustable via
Local control
-
Password panel control
- password protected but always possible (not regarded here).
Remark:
Direct panel control and local control via digital inputs are only active when the control station
sends AUTO MODE = 0.
Details see chapters 3.4 and 8.
continued