Universal Motor Controller UMC22-FBP
Software version 4.0
UMC22
0
V
10
24
V
11
24
V
12
DI
0
13
DI
1
14
DI
2
15
DI
3
16
DI
4
17
DI
5
18
5
DO
C
T1
T2 7
DO
0
6
DO
C
8
DO
1
9
DO
2
0 V
DI0 DI1* DI2* DI3 DI4 DI5
24 V
24 V
N
230 V
690 / 400 V
K1 K2
Fwd
2)
Off
3)
Rev
2)
K1
K1
K2
K2
T1 T2
external
supply
supply
inputs
2CDC 342 020 F0207
Control Panel
* transparent
to the fieldbus
Local operation via
digital inputs
1)
Multi-function input as Fault input: 0 = fault (closed circuit signal)
2)
Fwd, Rev: Momentary-contact switch (On)
3)
Off: 0 = dominating Off (closed circuit signal)
Fault
K1 = forward
K2 = reverse
7.4.1.2 Extended circuit
Main features
Parameters to be changed
(4.3.4)
(based on default)
Contactor K1 (forward) at output DO0
Control function = Reversing starter
Check-back by auxiliary contact at DI0
Check-back = Auxiliary contact
Contactor K2 (reverse) at output DO1
DI2 Multi-function input = 001
Fault input at DI2 (0 V signal = fault)
Fault output = On
Fault indication at output DO2
Local operation via DIs = On, 002, 003, 004,
008 or 009
Local control via digital inputs DI3, DI4, DI5
Set current 1
Overload protection parameters
Address
via Control Panel or Addressing Set
Illustration 7-9: UMC22-FBP: Control function = Reversing starter (Extended circuit)
Chapter 7.4.1~2 Revesing starter