- 142 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Par.
No.
Menu
No.
Menu point name
Display:
7-segm.
Default
Range
Description / remark
take over
-
1.3.8
Relay 0 check-
back fault
No 1-signal from auxiliary contact at
input DI0 within 300 ms after switching
on the contactor or 1-signal at input
DI0 even if contactor is not switched
on.
Assumption:
Check-back =
Auxiliary contacts
-
CTS 1
0 but not
CLS (Intermediate
position)
(Actuator)
Actuator only!
Closed torque signal appears (without
closed limit signal) in intermediate
position
1.3.9
Sametime
OLS and CLS
(Actuator)
Actuator only!
Closed limit signal and Open limit sig-
nal are present at the same time
1.3.10
Self test failed
Self test failed, e.g. CRC check not ok,
or was started during motor running.
Remark:
This fault can not be achnowledged.
1.3.11
Fault signal on DI0,
DI1 or DI2
At least one Multi-function input has
a fault signal (0-signal) e.g. from a
thermistor module.
Assumption:
At least one multi-function input is
parametrized as
Multi-function input =
P.001
(Fault signal always / not delay-
ed) (closed-circuit principle).
1.3.12
OLS 1
0 without
close command
(Actuator)
Actuator only!
Open limit signal disappears without
close command.
1.3.13
CLS 1
0 without
open command
(Actuator)
Actuator only!
Closed limit signal disappears without
open command.
1.3.14
OLS 1
0 not
within 3 s after
close command
(Actuator)
Actuator only!
Open limit signal does not disappear
within 3 s after close command
(7.8).
1.3.15
CLS 1
0 not
within 3 s after
open command
(Actuator)
Actuator only!
Closed limit signal does not isappear
within 3 s after open command
(7.8).
1.3.16
OTS 1
0 but not
OLS (Intermediate
position)
(Actuator)
Actuator only!
Open torque signal appears in inter-
mediate position (without Open limit
signal).
Chapter 8.2.1~3