- 17 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
24 V
0 V
UMC22
24
V
12
13
14
15
DI
2
16
17
18
DI
4
DI
5
DI
0
DI
1
DI
3
10
0
V
DO
C
5
6
DO
C
DO
0
7
DO
2
9
DO
1
8
max.
200 mA
K1
K2
K1
K2
K1
690 / 400 V AC
AC-15: 120 / 240 V
DC-13: 24 / 125 / 250 V N
T1 T2
T1 T2
0 V
24 V
24 V
24 V
11
24
V
2CDC 342 010 F0207
Contactor type
A45 and larger
Spark supression
Short circuit
protection
device
e.g. BS6-30-10-28 *
For check-back the auxiliary contact of the main contactor has to be used!
external
supply
supply
inputs
3.2.2 Connection of contactors (continued)
Interfacing contactors with peak current > 0,5 A: Types A50 and larger
Fig. 3-3: Connection of contactors with peak currents > 0.5 A (ABB types A50 and larger) to the UMC22-FBP
* This contactor has build in spark supression.
Chapter 3.2.2~2