- 23 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
3.3.3 Parametrization as a fi eldbus slave
Control systems, programming tools and the fi eldbus types are totally different.
This means:
There is no common rule to confi gure the fi eldbus master and to bind in FieldBusPlug
slaves into the application program.
Parametrization example:
UMC22-FBP connected to an ABB CPU type 07KT98 via PROFIBUS DP-V1 Plug PDP22-FBP:
The appropriate confi guration fi le is: ABB_082D.GSD. This fi le must be stored in the subdirectory ....
AC1131\Library\PLCConf.
The confi guration fi le contains the data for all available devices on the date of origin.
This means: For the PROFIBUS DP-V1 FieldBusPlug a list is offered during confi guration with all devices
that can be selected.
Other Programming Tools offer a menu point to read the .GSD confi guration fi le, or may request separate
confi guration fi les for different devices.
With the defi nition of the Byte addresses the addresses of the bits and words are automatically defi ned:
Telegram
data
Word (W)
Byte (B)
Bits (x)
Data bits 7...0
Input to
PLC
(Monitor)
%IW1.
4
%IB1.
8
%IB1.
9
%IX1.
4
.
0
... 1.
4
.
7
%IX1.
4
.
8
... 1.
4
.
15
WARNING ... RUN REVERSE
DI5 ... not used
%IW1.
5
%IB1.
10
%IB1.
11
%IX1.
5
.
0
... 1.
5
.
7
%IX1.
5
.
8
... 1.
5
.
15
Motor current, High Byte
Motor current, Low Byte
Output from
PLC
(Com-
mands)
%QW1.
8
%QB1.
16
%QB1.
17
%QX1.
8
.
0
... 1.
8
.
7
%QX1.
8
.
8
... 1.
8
.
15
WARNING ... RUN REVERSE
D=2 ... not used
%QW1.
9
%QB1.
18
%QB1.
19
%QX1.
9
.
0
... 1.
9
.
7
%QX1.
9
.
8
... 1.
9
.
15
... not used
... not used
coupler slot
/ 2
The confi guring tool of the 07KT98 CPU used for PROFIBUS DP-V1 also offers the list of the parameters
that can be changed:
Other control systems offer a more or less similar list.
For more info consult the appropriate FieldBusPlug and/or control system description.
Chapter 3.3.3~1
1 4
/ 2
8
4