- 154 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 8.2.3~4
Par.
No.
Menu
No.
Menu point name
Display:
7-segm.
Default
Range
Description / remark
take over
22
(Cont)
3.5.7
Local operation via
digital inputs and
direct control via
Control Panel
Local operation via DI3 und DI4:
motor on as long as button pressed.
DI5: closed circuit, pulse
Direct control via Control Panel
during
motor off
3.5.8
Local operation via
digital inputs and
direct control via
Control Panel
Local operation via DI3 und DI4:
motor on as long as button pressed.
DI5: true, pulse
Direct control via Control Panel
3.5.9
Local operation via
DI3, DI4, DI5 only
Local operation via DI3 und DI4:
motor on as long as button pressed.
DI5: closed circuit, pulse
3.5.10
Local operation via
DI3, DI4, DI5 only
Local operation via DI3 und DI4:
motor on as long as button pressed
DI5: true, pulse
13
3.6.
Check-back
(4.3.4)
during
motor off
3.6.0
Auxiliary contacts
Check-back OK, when auxiliary con-
tacts are closed 300 ms after start.
3.6.1
Motor current
current
Check-back OK, when current is
> 40 % of the set current is present
300 ms sfter start.
3.6.2
Simulation
Simulated check-back (e.g. to be set
to operation without motor).
Remark:
Normally overwritten by the control
system during power on (4.3).