- 86 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.0008
V 6
7.3.1.2 Extended circuit
Main features
Parameters to be changed
(4.3.4)
(based on default)
Contactor K1 at output DO0
Control function = Direct starter
Check-back by auxiliary contacts at input DI0
Check-back = Auxiliary contacts
Fault indication at output DO2
Fault output = On
Fault input at DI2 (0 V signal = fault)
DI2 Multi-function input = 001
Local control via inputs DI4 and DI5
Local operation via DIs= On, 002, 003, 004,
008 or 009
Set current 1
Overload protection parameters
Address
via Control Panel or Addressing Set
Illustration 7-6: UMC22-FBP: Control function = Direct starter (extended circuit)
UMC22
0
V
10
24
V
11
24
V
12
DI
0
13
DI
1
14
DI
2
15
DI
3
16
DI
4
17
DI
5
18
5
DO
C
T1
T2 7
DO
0
6
DO
C
8
DO
1
9
DO
2
0 V
DI0 DI1* DI2* DI3* DI4 DI5
24 V
24 V
N DO1
230 V
690 / 400 V
K1
Fwd
2)
Off
3)
K1
K1
T1 T2
external
supply
supply
inputs
2CDC 342 018 F0207
Control Panel
* transparent
to the fieldbus
Local operation via
digital inputs
1)
Multi-function input as Fault input: 0 = fault (closed circuit signal)
2)
Fwd: Momentary-contact switch (On)
3)
Off: 0 = dominating Off (closed circuit signal)
Fault
Chapter 7.3.1~2 Direct starter