TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
66
Note Register
Address
Item Description
3 10058:
Reserved
Reserved
3 10059:
Reserved
Reserved
3 10060:
Reserved
Reserved
3 10061:
Reserved
Reserved
3 10062:
Reserved
Reserved
3 10063:
Reserved
Reserved
3 10064:
Reserved
Reserved
3
10065:
51P-3
Winding 3 Phase Time Overcurrent Control Enabled
3
10066:
51N-3
Winding 3 Neutral Time Overcurrent Control Enabled
3 10067: 50P-3
1
st
Winding 3 Phase Time Instantaneous Control Enabled
3 10068: 50N-3
1
st
Winding 3 Neutral Time Instantaneous Control Enabled
3 10069: 150P-3
2
nd
Winding 3 Phase Time Instantaneous Control Enabled
3 10070: 150N-3
2
nd
Winding 3 Neutral Time Instantaneous Control Enabled
3
10071:
46-3
Winding 3 Negative Sequence Control Enabled
3
10072:
51G
Ground Time Overcurrent Control Enabled
3
10073:
50G
Ground Time Instantaneous Control Enabled
3= 3 Winding TPU Only
Physical Inputs (16 Elements Defined)
Physical inputs are map-able for various functional inputs. Input status correlates to the state of the input seen at
the physical terminals of the TPU2000/2000R their status is available at the following addresses as illustrated in
Table 5-6.
Table 5-6. Physical Input Modbus Address Map Definition
Notes Register Address
Item
Description
10257:
Reserved
Reserved
10258:
Reserved
Reserved
10259:
Reserved
Reserved
10260:
Reserved
Reserved
10261:
Reserved
Reserved
10262:
Reserved
Reserved
10263
Reserved
Reserved
10264
IN9
Physical Input 9
10265:
IN8
Physical Input 8
10266:
IN7
Physical Input 7
10267:
IN6
Physical Input 6
10268:
IN5
Physical Input 5
10269:
IN4
Physical Input 4
10270: IN3
Physical Input 3
10271: IN2
Physical Input 2
10272: IN1
Physical Input 1
Momentary Change Detect Logical Inputs (68 Elements Defined 2 Winding TPU - 160
Elements Defined 3 Winding TPU)
Whereas the information presented in Tables 5-5 and 5-6 illustrate the real time status of the designated data
points, the status in Table 5-7 lists the data in Momentary Change Detect status. The momentary change detect
decoding follows the same philosophy as that presented in Section 5 for the 0X logical and physical data
presentation.
Table 5-7. Logical Input Status Momentary Change Detect Status
Notes Register
Address
Item Description