TPU2000/2000R Modbus/Modbus Plus Automation Guide
59
Register
Address
Item Description
00009
TFA
Trip Fail Alarm Energized
00010
51P-1
Winding 1 Phase Time Overcurrent Alarm Energized
00011
51P-2
Winding 2 Phase Time Overcurrent Alarm Energized
00012
50P-1
1
st
Winding 1 Phase Instantaneous Overcurrent Trip Alarm Energized
00013
150P-1 2
nd
Winding 1 Phase Instantaneous Overcurrent Trip Alarm Energized
00014
50P-2
1
st
Winding 2 Phase Instantaneous Overcurrent Trip Alarm Energized
00015
150P-2 2
nd
Winding 2 Phase Instantaneous Overcurrent Trip Alarm Energized
00016
51N-1
Winding 1 Neutral Time Overcurrent Trip Alarm Energized
00017
51N-2
Winding 1 Neutral Time Overcurrent Trip Alarm Energized
00018
50N-1
1
st
Winding 1 Neutral Instantaneous Overcurrent Trip Alarm Energized
00019
150N-1 2
nd
Winding 1 Neutral Instantaneous Overcurrent Trip Alarm Energized
00020
50N-2
1
st
Winding 2 Neutral Instantaneous Overcurrent Trip Alarm Energized
00021
150N-2 2
nd
Winding 2 Neutral Instantaneous Overcurrent Trip Alarm Energized
00022
46-1
Winding 1 Negative Sequence Time Overcurrent Trip Alarm Energized
00023
46-2
Winding 1 Negative Sequence Time Overcurrent Trip Alarm Energized
00024
87T-D
Percentage Differential Disabled Alarm Energized
00025
87H-D
High Set Instantaneous Function Disabled Alarm Energized
00026
51P-1D
Winding 1 Phase Time Overcurrent Function Disabled Alarm
00027
51P-2D
Winding 2 Phase Time Overcurrent Function Disabled Alarm
00028
51N-1D
Winding 1 Neutral Time Overcurrent Function Disabled Alarm
00029
51N-2D
Winding 2 Neutral Time Overcurrent Function Disabled Alarm
00030
50P-1D 1
st
Winding 1 Phase Instantaneous Overcurrent Function Disabled Alarm
00031
50P-2D 1
st
Winding 2 Phase Instantaneous Overcurrent Function Disabled Alarm
00032
50N-1D 1
st
Winding 1 Neutral Instantaneous Overcurrent Function Disabled Alarm
00033
50N-2D 1
st
Winding 2 Neutral Instantaneous Overcurrent Function Disabled Alarm
00034
150P-1D 2
nd
Winding 1 Phase Instantaneous Overcurrent Function Disabled Alarm
00035
150P-2D 2
nd
Winding 2 Phase Instantaneous Overcurrent Function Disabled Alarm
00036
150N-1D 2
nd
Winding 1 Neutral Instantaneous Overcurrent Function Disabled Alarm
00037
150N-2D 2
nd
Winding 2 Neutral Instantaneous Overcurrent Function Disabled Alarm
00038
46-1D
Winding 1 Negative Sequence Time Overcurrent Function Disabled Alarm
00039
46-2D
Winding 1 Negative Sequence Time Overcurrent Function Disabled Alarm
00040
PATA
Phase A Target Alarm Energized
00041
PBTA
Phase B Target Alarm Energized
00042
PCTA
Phase C Target Alarm Energized
00043
PUA
Pick Up Alarm Energized
00044
63
Sudden Pressure Input Alarm Energized
00045
THRUFA
Through Fault Alarm Energized
00046
TFCA
Through Fault Counter Alarm Energized
00047
TFKA-2
Through Fault KiloAmp Symmetrical Alarm Winding 2 Energized
00048
TFSCA
Through Fault Summation Cycle Alarm Energized
00049
DTC
Differential Trip Current Alarm Energized
00050
OCTC
Overcurrent Trip Counter Alarm Energized
00051
PDA
Phase Demand Current Alarm Energized
00052
NDA
Neutral Demand Current Alarm Energized
00053
PRIM
Primary Settings Alarm Energized
00054
ALT1
Alternate 1 Settings Enabled
00055
ALT2
Alternate 2 Settings Enabled
00056
STCA
Settings Table Changed Alarm Energized
(L)
00057
87T
Harmonic Restrained % Differential Trip Alarm Energized
(L)
00058
87H
Unrestrained High Set Instantaneous Differential Trip Alarm Energized
(L)
00059 2HROA
2
nd
Harmonic Restraint Alarm Energized
(L)
00060 5HROA
5
th
Harmonic Restraint Alarm Energized
(L)
00061
AHROA
All Harmonics Restraint Alarm (2
nd
through 11th Harmonic) Energized
(L)
00062
51P-1
Winding 1 Phase Time Overcurrent Alarm Energized