TPU2000/2000R Modbus/Modbus Plus Automation Guide
193
ANSI Curve Selection Type I
ANSI Curve Type II
0 = Extremely Inverse
0 = Disable
1
=
Very
Inverse
1
=
Standard
2 = Inverse
2 = Inverse
3 = Short Time Inverse 3
=
Definite
Time
4 = Definite Time
4 = Short Time Inverse
5 = Long Time Extremely Inverse
5 = Short Time Extremely Inverse
6 = Long Time Very Inverse
6 = User Curve 1
7 = Long Time Inverse
7 = User Curve 2
8 = Recloser Curve
8 = User Curve 3
9 = Disabled
1
0 = User Curve 1
11 = User Curve 2
12 = User Curve 3
ANSI Curve Selection 87T
Mode Selection Type 87T
0
=
Disable
0
=
Disabled
1 = Percent Slope
1 = 2
nd
Harmonics
2 = HU 30%
2 = 2
nd
and 5
th
Harmonics
3 = HU 35%
3 = All Harmonics
4 = Percent 15% Tap
5 = Percent 25% Tap
6 = Percent 40% Tap
7 = User Curve 1
8 = User Curve 2
9 = User Curve 3
Table 5-66 lists the register assignments for the 6X registers for the Primary Settings Group Functions.
Table 5-66. Primary Settings Register Definition Common to the 2 and 3 Winding Units
Register
Address
Item Description
61024 SPARE_1
61025 Execute
Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
Unsigned 16 Bits
61026
Access Password
ASCII – 2 Characters Leftmost Digits
61027
Access Password
ASCII – 2 Characters Rightmost Digits
61028 SPARE_2
61029
87T Curve Type
Unsigned Integer 16 Bits
61030
87T Minimum I Operate
Unsigned 16 Bits
0.2 <=Range <=1.0 (X10)
61031
87T Percent Restraint
15<=Range<=60
61032
87T Restraint Mode
Unsigned Integer 16 Bits
Refer to Mode Selection Table
61033 87T
2
nd
Harmonic Restraint
Unsigned Integer 16 Bits
7.5<=Range<=25 (X10)
61034 87T
5
th
Harmonic Restraint
Unsigned Integer 16 Bits
15<=Range<=40 (X10)
61035
87T All Harmonic Restraint
Unsigned Integer 16 Bits
15<=Range<=40 (X10)
61036
87H Tap X Byte
Unsigned Integer 16 Bits
6 <=Range<=20 (X10)
61037
87T-1 Amp
Unsigned Integer 16 Bits
2<=Range<=9 (X10)
0.4<=Range<=1.8 (X50)