TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
52
Register
Address
Item Description
00590:
46-2D MOMENTARY
Winding 1 Negative Sequence Time Overcurrent Function
Disabled Alarm (Momentary)
00591:
PATA STATUS
Phase A Target Alarm Energized (Status)
00592:
PATA MOMENTARY
Phase A Target Alarm Energized (Momentary)
00593:
PBTA STATUS
Phase B Target Alarm Energized (Status)
00594:
PBTA MOMENTARY
Phase B Target Alarm Energized (Momentary)
00595:
PCTA STATUS
Phase C Target Alarm Energized (Status)
00596:
PCTA MOMENTARY
Phase C Target Alarm Energized (Momentary)
00597:
PUA STATUS
Pick Up Alarm Energized (Status)
00598:
PUA MOMENTARY
Pick Up Alarm Energized (Momentary)
00599:
63 STATUS
Sudden Pressure Input Alarm Energized (Status)
00600:
63 MOMENTARY
Sudden Pressure Input Alarm Energized (Momentary)
00601:
THRUFA STATUS
Through Fault Alarm Energized (Status)
00602:
THRUFA MOMENTARY
Through Fault Alarm Energized (Momentary)
00603:
TFCA STATUS
Through Fault Counter Alarm Energized (Status)
00604:
TFCA MOMENTARY
Through Fault Counter Alarm Energized (Momentary)
00605:
TFKA-2 STATUS
Through Fault KiloAmp Symmetrical Alarm Winding 2
Energized. (Status)
00606:
TFKA-2 MOMENTARY
Through Fault KiloAmp Symmetrical Alarm Winding 2
Energized. (Momentary)
00607:
TFSCA STATUS
Through Fault Summation Cycle Alarm Energized (Status)
00608:
TFSCA MOMENTARY
Through Fault Summation Cycle Alarm Energized
(Momentary)
00609:
DTC STATUS
Differential Trip Current Alarm Energized (Status)
00610:
DTC MOMENTARY
Differential Trip Current Alarm Energized (Momentary)
00611:
OCTC STATUS
Overcurrent Trip Counter Alarm Energized (Status)
00612:
OCTC MOMENTARY
Overcurrent Trip Counter Alarm Energized (Momentary)
00613:
PDA STATUS
Phase Demand Current Alarm Energized (Status)
00614:
PDA MOMENTARY
Phase Demand Current Alarm Energized (Momentary)
00615:
NDA STATUS
Neutral Demand Current Alarm Energized (Status)
00616:
NDA MOMENTARY
Neutral Demand Current Alarm Energized (Momentary)
00617:
PRIM STATUS
Primary Settings Alarm Energized (Status)
00618:
PRIM MOMENTARY
Primary Settings Alarm Energized (Momentary)
00619:
ALT1 STATUS
Alternate 1 Settings Enabled (Status)
00620:
ALT1 MOMENTARY
Alternate 1 Settings Enabled (Momentary)
00621:
ALT2 STATUS
Alternate 2 Settings Enabled (Status)
00622:
ALT2 MOMENTARY
Alternate 2 Settings Enabled (Momentary)
00623:
STCA STATUS
Settings Table Changed Alarm Energized (Status)
00624:
STCA MOMENTARY
Settings Table Changed Alarm Energized (Momentary)
(L)
00625:
87T STATUS
Harmonic Restrained % Differential Trip Alarm Energized
(Status)
(L)
00626:
87T MOMENTARY
Harmonic Restrained % Differential Trip Alarm Energized
(Momentary)
(L)
00627:
87H STATUS
Unrestrained High Set Instantaneous Differential Trip Alarm
Energized (Status)
(L)
00628:
87H MOMENTARY
Unrestrained High Set Instantaneous Differential Trip Alarm
Energized (Momentary)
(L)
00629: 2HROA
STATUS
2
nd
Harmonic Restraint Alarm Energized (Status)
(L)
00630: 2HROA
MOMENTARY 2
nd
Harmonic Restraint Alarm Energized (Momentary)
(L)
00631: 5HROA
STATUS
5
th
Harmonic Restraint Alarm Energized (Status)
(L)
00632: 5HROA
MOMENTARY 5
th
Harmonic Restraint Alarm Energized (Momentary)
(L)
00633:
AHROA STATUS
All Harmonics Restraint Alarm (2
nd
through11th Harmonic)
Energized (Status)
(L)
00634: AHROA
MOMENTARY All Harmonics Restraint Alarm (2
nd
through11th Harmonic)