TPU2000/2000R Modbus/Modbus Plus Automation Guide
207
Register
Address
Item Description
63483
51G-3 Curve Select (TYPE II)
Unsigned 16 Bits
Range 0-12 (See Text Above)
63484
51G-3 Pickup Amps
Unsigned 16 Bits
1<=Range<= 12 *10
0.2<=Range<=2.4 Amp * 50 (See Note)
63485
51G-3 Time Dial/Time Delay
Unsigned 16 Bits
1<=Range <=10 * 20 : Time Dial
0<=Range<=10 * 20 : Time Delay
63486
50G-3 Curve Select Byte (TYPE II) Unsigned Integer 16 bits
0<=Range<=12 (See Text Above)
63487
51G-3 Pickup Amps
Unsigned 16 Bits
0.5<=Range<= 20 *10
63488
51G-3 Time Dial/Delay Setting
Unsigned 16 Bits
Time Dial * 10
Delay * 100
63489
150G-3 Curve Select (TYPE II)
Unsigned Integer 16 bits
See Table Above
63490
150G-3 Pickup Amps
Unsigned 16 Bits
0.5<=Range<= 20 *10
63491
150G-3 Time Delay
Unsigned 16 Bits
0<=Range<=9.99 * 100
63492
Disturb 3 Pickup X
Unsigned Integer 16 Bits
0.5<= Range<=5 *10
63493
Level Detector-1 Pickup X
Unsigned Integer 16 Bits
0.5<= Range<=20 *10 , 201 = Disable
Configuration Settings
The TPU2000 and TPU2000R has configuration settings which may be set through the unit’s Front Panel
Interface (FPI), ECP (External Communication Program), WinECP (WINdows External Communication Program)
or via Modbus/Modbus Plus via Registers 61458 through 61445. Table 5-72 is for the TPU2000 2 Winding units
and the TPU2000R 2 and 3 Winding Units.
Table 5-72. TPU2000/2000R Configuration Setting Register Setting
Register
Address
Item Description
61408 SPARE_1
61409 Execute
Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
Unsigned 16 Bit
61410
Access Password
ASCII – 2 Characters Leftmost Digits
61411
Access Password
ASCII – 2 Characters Rightmost Digits
61412 SPARE_2
61413
Winding 1 Phase CT Ratio
Unsigned Integer 16 Bits
1<=Range<=4000
61414
Winding 1 Neutral CT Ratio
Unsigned Integer 16 Bits
1<=Range<=4000
61415
Winding 2 Phase CT Ratio
Unsigned Integer 16 Bits
1<=Range<=4000
61416
Winding 2 Neutral CT Ratio
Unsigned Integer 16 Bits
1<=Range<=4000
61417
Winding Phase Comp
Unsigned Integer 16 Bits