TPU2000/2000R Modbus/Modbus Plus Automation Guide
53
Register
Address
Item Description
Energized (Momentary)
(L)
00635:
51P-1 STATUS
Winding 1 Phase Time Overcurrent Alarm Energized (Status)
(L)
00636:
51P-1 MOMENTARY
Winding 1 Phase Time Overcurrent Alarm Energized
(Momentary)
(L)
00637:
51P-2 STATUS
Winding 2 Phase Time Overcurrent Alarm Energized (Status)
(L)
00638:
51P-2 MOMENTARY
Winding 2 Phase Time Overcurrent Alarm Energized
(Momentary)
(L)
00639:
50P-1 STATUS
1
st
Winding 1 Phase Instantaneous Overcurrent Trip Alarm
Energized (Status)
(L)
00640: 50P-1
MOMENTARY
1
st
Winding 1 Phase Instantaneous Overcurrent Trip Alarm
Energized (Momentary)
(L)
00641: 150P-1
STATUS
2
nd
Winding 1 Phase Instantaneous Overcurrent Trip Alarm
Energized (Status)
(L)
00642: 150P-1
STATUS
2
nd
Winding 1 Phase Instantaneous Overcurrent Trip Alarm
Energized (Status)
(L)
00643: 50P-2
1
st
Winding 2 Phase Instantaneous Overcurrent Trip Alarm
Energized
(L)
00644: 50P-2
1
st
Winding 2 Phase Instantaneous Overcurrent Trip Alarm
Energized
(L)
00645: 150P-2
2
nd
Winding 2 Phase Instantaneous Overcurrent Trip Alarm
Energized
(L)
00646: 150P-2
2
nd
Winding 2 Phase Instantaneous Overcurrent Trip Alarm
Energized
(L)
00647:
51N-1
Winding 1 Neutral Time Overcurrent Trip Alarm Energized
(L)
00648:
51N-1
Winding 1 Neutral Time Overcurrent Trip Alarm Energized
(L)
00649:
51N-2
Winding 1 Neutral Time Overcurrent Trip Alarm Energized
(L)
00650:
51N-2
Winding 1 Neutral Time Overcurrent Trip Alarm Energized
(L)
00651: 50N-1
1
st
Winding 1 Neutral Instantaneous Overcurrent Trip Alarm
Energized
(L)
00652: 50N-1
1
st
Winding 1 Neutral Instantaneous Overcurrent Trip Alarm
Energized
(L)
00653: 150N-1
2
nd
Winding 1 Neutral Instantaneous Overcurrent Trip Alarm
Energized
(L)
00654: 150N-1
2
nd
Winding 1 Neutral Instantaneous Overcurrent Trip Alarm
Energized
(L)
00655: 50N-2
1
st
Winding 2 Neutral Instantaneous Overcurrent Trip Alarm
Energized
(L)
00656: 50N-2
1
st
Winding 2 Neutral Instantaneous Overcurrent Trip Alarm
Energized
(L)
00657: 150N-2
2
nd
Winding 2 Neutral Instantaneous Overcurrent Trip Alarm
Energized
(L)
00658: 150N-2
2
nd
Winding 2 Neutral Instantaneous Overcurrent Trip Alarm
Energized
(L)
00659:
46-1
Winding 1 Negative Sequence Time Overcurrent Trip Alarm
Energized
(L)
00660:
46-1
Winding 1 Negative Sequence Time Overcurrent Trip Alarm
Energized
(L)
00661:
46-2
Winding 1 Negative Sequence Time Overcurrent Trip Alarm
Energized
(L)
00662:
46-2
Winding 1 Negative Sequence Time Overcurrent Trip Alarm
Energized
(L)
00663:
63
Sudden Pressure Seal In Alarm Energized
(L)
00664:
63
Sudden Pressure Seal In Alarm Energized
00665:
ULO 1
User Logical Output 1
00666:
ULO 1
User Logical Output 1