TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
188
LO
Lo Bit Mask
60541
FEEDBACK 7 SELECT MASK
HI
Unsigned Integer 16 Bits
Hi Bit Mask
60542
FEEDBACK 7 SELECT MASK
LO
Unsigned Integer 16 Bits
Lo Bit Mask
60543
FEEDBACK 8 SELECT MASK
HI
Unsigned Integer 16 Bits
Hi Bit Mask
60544
FEEDBACK 8 SELECT MASK
LO
Unsigned Integer 16 Bits
Lo Bit Mask
Table 5-63 lists the programmable Output Select and Index Bytes required for selecting the Output required as per
Figure 5-68. Note a bit value of 1 means the bit is de-selected, a bit value of 0 means the bit is selected.
Bit
Position: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
TPU2000(R)
: OT15 OT14 OT13 OT12 OT11 0T10 OT9 OT8 OT7 OT6 OT5 OT4 OT3 OT2 OT1 N/A
Figure 5-67. Low Bit Mask Output Mapping Definition for Registers
Bit
Position: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
TPU2000(R)
: OT
31
OT
30
OT
29
OT
28
OT
27
OT
26
OT
25
OT
24
OT
23
OT
22
OT
21
OT
20
OT
19
OT
18
OT
17
OT
16
Figure 5-68. High Bit Mask Output Mapping Definition for Registers
Function Index Table and Definition
Table 5-62. Physical Logical Function Byte Configuration Codes for Registers 60044 to 60058
Index
(decimal)
Input Definition
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
TRIP
CLOSE
ALARM
27-1P
46
50P-1
50N-1
50P-2
50N-2
50P-3
50N-3
51P
51N
59
67P
67N
81S-1
81R-1
PATA
PBTA
PCTA
TCFA
TCC
79DA
PUA
79LOA
BFA
PDA
Fixed Trip
Fixed Close
Self Check Alarm
Single Phase Under Voltage
Negative Sequence Overcurrent
Phase Inst. Overcurrent
Neutral Inst. Overcurrent
Phase Inst. Overcurrent
Neutral Inst. Overcurrent
Phase Inst. Overcurrent
Neutral Inst. Overcurrent
Phase Inst. Overcurrent
Neutral Inst. Overcurrent
Over Voltage
Directional Overcurrent (pos seq)
Directional Overcurrent (neg seq)
Frequency Shed (First stage)
Frequency Restore (First stage)
Phase A Target
Phase B Target
Phase C Target
Trip Circuit Fail
Tap Changer Cutout
Recloser Disable
Pickup
Recloser Lockout
Breaker Fail
Phase Peak Demand