TPU2000/2000R Modbus/Modbus Plus Automation Guide
8
1
Horizontal Unit Mounting – Front panel LCD interface is included.
5
Vertical Unit Mounting – No front panel LCD interface.
6
Vertical Unit Mounting – Front panel LCD interface is included.
IF PART
NUMBER
POSITION “Z” IS
THE TPU2000R HAS AN INSTALLED OPTION
For unit
5 8 8 X X X Y
Z
– X X X X
Q ( X = Don’t Care)
(COMMUNICATION PHYSICAL INTERFACE OPTION)
0
RS232 (COM 1) Non-Isolated Port is active on the unit.
1
RS232 (COM 2) Isolated Port Only is active on the unit.
(SEE NOTE)
2
RS485 (AUX COM PORT) and RS232 (COM 3) Ports on Option Card.
3
INCOM (AUX COM PORT) and RS485 (AUX COM PORT) Ports on Option Card.
4
INCOM (AUX COM PORT) and RS485 (AUX COM PORT) Ports on Option Card.
5
RS485 (AUX COM PORT) Port On Option Card.
6
Modbus Plus Port (COM 3) on the Option Card.
7
Modbus Plus (COM 3) and RS485 (AUX COM PORT) on the Option Card.
8
RS485 (COM 3) and RS485 (AUX COM PORT) Ports on the Option Card.
E
Ethernet Fiber Optic and Copper Option Card (Available on the 2 Winding TPU
Unit Only)
NOTE: * = If the option denoted in part number position “Y” is a 0 or 5, the COM 2
port is enabled, if the option denoted in part number position “Y” is a 2 or 6 the
COM 2 Port is disabled.
IF PART
NUMBER
POSITION “Q” IS
THE TPU2000R HAS AN INSTALLED OPTION
For unit
5 8 8 X X X Y
Z
– X X X X
Q
(X = Don’t Care)
(COMMUNICATION PHYSICAL INTERFACE OPTION)
0 STANDARD
TEN
BYTE
1 DNP
3.0
4
Serial Modbus/Modbus Plus/TCP/IP Modbus (Depending on hardware interface
selected in Position Z)
Table 2-4. TPU2000R Communication Card Matrix for Unit 5 8 8 X X X Y Z – X X X X Q
“Z”
Digit
“Q”
Digit
COM 1
RS232
COM 2
RS232
COM 3
AUX COM
RS485
INCOM
Time
Synch
0
0
Note 1
Standard 10 Byte
1
0
Note 1
Standard 10 Byte
RS232
2
0
Note 1
Standard 10 Byte
RS232
Standard 10 Byte
IRIG B
2
1
Note 1
Standard 10 Byte or
DNP 3.0
RS232
Standard 10 Byte
or DNP 3.0
2
4
Note 1
Standard 10 Byte or
Modbus
RS232
Standard 10 Byte
or Modbus
IRIG
B
3
0
Note
1
Available
IRIG
B
4
0
Note 1
Standard 10 Byte Available IRIG B
4
1
Note 1
DNP 3.0
Available IRIG B
4
4
Note 1
Modbus
Available IRIG B
5
0
Note 1
Standard 10 Byte
6
4
Note 1
Standard 10 Byte Modbus Plus
7
4
Note 1
Modbus Plus
Standard 10 Byte
8
0
Note 1
Standard 10 Byte
RS485
Standard 10 Byte
IRIG B
8
1
Note 1
Standard 10 Byte or
DNP 3.0
RS485
Standard 10 Byte
or DNP 3.0
8
4
Note 1
Standard 10 Byte or
Modbus
RS485
Standard 10 Byte
or Modbus
IRIG
B
E
4
Note 1
TCP/IP Modbus
Ethernet Copper
SNTP