TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
302
169
ULI4
Input
Opened
170
ULI5 Input Closed
171
ULI5
Input
Opened
172
ULI6 Input Closed
173
ULI6
Input
Opened
174
ULI7 Input Closed
175
ULI7
Input
Opened
176
ULI8 Input Closed
177
ULI8
Input
Opened
178
ULI9 Input Closed
179
ULI9
Input
Opened
180
CRI Input Closed
181
CRI
Input
Opened
Msg byte Definition
1/1
Relay Status (see command 3 4 1, msg 1/1)
1/2
C Subcommand = 0x5c
1/3
Total Number of Messages = 5
2/1
Year
2/2
Month
2/3
Day
3/1
Hour
3/2
Minute
3/3
Second
4/1
Hundredths of second
4/2
Message Number
4/3
Value (if any) Hi byte
5/1
Value (if any) Lo byte
5/2
Operation Number (high byte)
5/3
Operation Number (low byte)
If the operation entry doesn't exist then send 0's in all the bytes 2/1 through 5/3.
5.13 Send Next Operations Record ( 3 5 13 )
Same format as ( 3 5 12 ) except Msg 1/2 = 0x5d.
5.14 Breaker Status (Including I/O Status) ( 3 5 14 )
Input status bit 0=opened, 1=closed.
Output status bit 0=de-energized, 1=energized.
Msg byte Definition
1/1
Relay Status (see command 3 4 1, msg 1/1)
1/2
C Subcommand = 0x5e
1/3
Total Number of Messages = 3
2/1
Contact Input Status (high byte)
Bit 0 - Input 9
Bit 1 - Spare
Bit 2 - Spare
Bit 3 - Spare
Bit 4 - Spare
Bit 5 - Spare
Bit 6 - Spare
Bit 7 - Spare
2/2
Contact Input Status (low byte)
Bit 0 - Input 1
Bit 1 - Input 2
Bit 2 - Input 3