TPU2000/2000R Modbus/Modbus Plus Automation Guide
165
Register
Address
3 Winding
Item Description
50 or 60 Hz
SAMPLE RATE INFORMATION
42707 Reserved
Reserved
42708 Reserved
Reserved
42709 Reserved
Reserved
CHANNEL NAMES, UNITS, AND CONVERSIONS
42710
CHANNEL 1 – Channel Number
Unsigned Integer 16 Bits
See Note 1
42711
CHANNEL 1 – Channel Name
2 Digits ASCII
42712
CHANNEL 1 – Channel Phase
Identification
Unsigned Integer 16 Bits
See Note 1
42713
CHANNEL 1 – Channel Units
Unsigned Integer 16 Bits
1 = Amps
2 = Volts
42714
CHANNEL 1 – Scale Factor Numerator
Unsigned 32 Bit High Order Word (MSW)
42715
CHANNEL 1 – Scale Factor Numerator
Unsigned 32 Bit Low Order Word (LSW)
42716
CHANNEL 1 – Scale Factor Denominator)
Unsigned 32 Bit High Order Word ( MSW)
42717
CHANNEL 1 – Scale Factor Denominator
Unsigned 32 Bit Low Order Word (MSW)
42718
CHANNEL 2 – Channel Number
Unsigned Integer 16 Bits
See Note 1
42719
CHANNEL 2 – Channel Name
2 Digits ASCII
42720
CHANNEL 2 – Channel Phase
Identification
Unsigned Integer 16 Bits
See Note 1
42721
CHANNEL 2 – Channel Units
Unsigned Integer 16 Bits
1 = Amps
2 = Volts
42722
CHANNEL 2 – Scale Factor Numerator
Unsigned 32 Bit High Order Word (MSW)
42723
CHANNEL 2 – Scale Factor Numerator
Unsigned 32 Bit Low Order Word (LSW)
42724
CHANNEL 2 – Scale Factor Denominator
Unsigned 32 Bit High Order Word (MSW)
42725
CHANNEL 2 – Scale Factor Denominator
Unsigned 32 Bit Low Order Word (MSW)
42726
CHANNEL 3 – Channel Number
Unsigned Integer 16 Bits
See Note 1
42727
CHANNEL 3 – Channel Name
2 Digits ASCII
42728
CHANNEL 3 – Channel Phase
Identification
Unsigned Integer 16 Bits
See Note 1
42729
CHANNEL 3 – Channel Units
Unsigned Integer 16 Bits
1 = Amps
2 = Volts
42730
CHANNEL 3 – Scale Factor Numerator
Unsigned 32 Bit High Order Word (MSW)
42731
CHANNEL 3 – Scale Factor Numerator
Unsigned 32 Bit Low Order Word (LSW)
42732
CHANNEL 3 – Scale Factor Denominator
Unsigned 32 Bit High Order Word ( MSW)
42733
CHANNEL 3 – Scale Factor Denominator
Unsigned 32 Bit Low Order Word (MSW)
42734
CHANNEL 4 – Channel Number
Unsigned Integer 16 Bits
See Note 1
42735
CHANNEL 4 – Channel Name
2 Digits ASCII
42736
CHANNEL 4 – Channel Phase
Identification
Unsigned Integer 16 Bits
See Note 1
42737
CHANNEL 4 – Channel Units
Unsigned Integer 16 Bits
1 = Amps
2 = Volts
42738
CHANNEL 4 – Scale Factor Numerator
Unsigned 32 Bit High Order Word (MSW)
42739
CHANNEL 4 – Scale Factor Numerator
Unsigned 32 Bit Low Order Word (LSW)
42740
CHANNEL 4 – Scale Factor Denominator
Unsigned 32 Bit High Order Word (MSW)
42741
CHANNEL 4 – Scale Factor Denominator
Unsigned 32 Bit Low Order Word (MSW)