TPU2000/2000R Modbus/Modbus Plus Automation Guide
103
Register
Address
Item Description
Month
00<= Range <= 12
40945 Minimum
Demand
KVAR Hours (Phase B)
Day
Most Significant Byte 8 Bits
00<= Range<= 31
40945 Minimum
Demand
KVAR Hours (Phase B)
Hour
Most Significant Byte 8 Bits
00<= Range <= 23
40946 Minimum
Demand
KVAR Hours (Phase B)
Minute
Most Significant Byte 8 Bits
00<= Range <= 59
40946 Reserved
Byte
Reserved
40947
KVAR Hours (Phase C) Minimum Demand Signed 32 Bit High Order Word MSW
40948
KVAR Hours (Phase C) Minimum Demand
Signed 32 Bit Low Order Word LSW
40949 Minimum
Demand
KVAR Hours (Phase C)
Year
Most Significant Byte 8 Bits
00<= Range <= 99
40949 Minimum
Demand
KVAR Hours (Phase C)
Month
Least Significant Byte 8 Bits
00<= Range <= 12
40950 Minimum
Demand
KVAR Hours (Phase C)
Day
Most Significant Byte 8 Bits
00<= Range<= 31
40950 Minimum
Demand
KVAR Hours (Phase C)
Hour
Most Significant Byte 8 Bits
00<= Range <= 23
40951 Minimum
Demand
KVAR Hours (Phase C)
Minute
Most Significant Byte 8 Bits
00<= Range <= 59
40951 Reserved
Byte
Reserved
40952
KVAR Hours (3 Phase) Minimum Demand Signed 32 Bit High Order Word MSW
40953
KVAR Hours (3 Phase) Minimum Demand
Signed 32 Bit Low Order Word LSW
40954
Minimum Demand KVAR Hours (3 Phase)
Year
Most Significant Byte 8 Bits
00<= Range <= 99
40954
Minimum Demand KVAR Hours (3 Phase)
Month
Least Significant Byte 8 Bits
00<= Range <= 12
40955
Minimum Demand KVAR Hours (3 Phase)
Day
Most Significant Byte 8 Bits
00<= Range<= 31
40955
Minimum Demand KVAR Hours (3 Phase)
Hour
Most Significant Byte 8 Bits
00<= Range <= 23
40956
Minimum Demand KVAR Hours (3 Phase)
Minute
Most Significant Byte 8 Bits
00<= Range <= 59
40956 Reserved
Byte
Reserved
Breaker Counters (11 Registers Defined) Modbus Function 03 Read Only
Breaker Counters allow diagnostic evaluation of operations for maintenance purposes The TPU2000/2000R
allows selection of reclosure for up to 4 shots with the fifth event initiating lockout. The counter registers are reset
via a write to registers 63713 through 63719 as defined in Table 5-25. Table 5-25 defines the register map for the
Breaker Counter capabilities within the unit. Additionally, unreported fault record counts are available. This is
especially helpful when accessing fault buffers (using the unreported records command) and knowing the amount
of records yet to be accessed.
Table 5-25. Breaker Counter Definition Table
Register
Address
Item Description
41025
Unreported Differential Fault Record
Counter
Unsigned Integer 16 Bits
0<=Range<=9999
41026
Unreported Through Fault Record Counter
Unsigned Integer 16 Bits
0<=Range<=9999
41027
Unreported Harmonic Restraint Record
Fault Counter
Unsigned Integer 16 Bits
0<=Range<= 9999
41028
Unreported Operation Record Counter
Unsigned Integer 16 Bits