TPU2000/2000R Modbus/Modbus Plus Automation Guide
209
3 = 60
61438
LCD Contrast Adjust
Unsigned Integer 16 Bits
0<=Range <= 63
61439
Relay Password
ASCII – 2 Characters Leftmost Digits
61440
Relay Password
ASCII – 2 Characters Rightmost Digits
61441
Test Password
ASCII – 2 Characters Leftmost Digits
61442
Test Password
ASCII – 2 Characters Rightmost Digits
61443
Meter Winding Mode
Unsigned Integer
0 = Winding 1
1 = Winding 2
2 = Winding 3
61444
VT Configuration
Unsigned Integer 16 Bits
0 = 69 V Wye
1 = 120V Wye
2 = 120V Delta
3 = 208 V Delta
61445
VT Ratio
Unsigned Integer 16 Bits
1<=Range<=45000
The Configuration Files for the 3 Winding TPU2000R is as follows:
Table 5-73. TPU2000/2000R Configuration Setting Register Setting
Register
Address
Item Description
63584 SPARE_1
63585 Execute
Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
Unsigned 16 Bit
63586
Access Password
ASCII – 2 Characters Leftmost Digits
63587
Access Password
ASCII – 2 Characters Rightmost Digits
63588 SPARE_2
63589
Winding 3 Phase CT Ratio
Unsigned Integer 16 Bits
1<=Range<=4000
63590
Winding 3 Neutral CT Ratio
Unsigned Integer 16 Bits
1<=Range<=4000
63591
Winding 3 Ground CT Ratio
Unsigned Integer 16 Bits
1<=Range<=4000
63592
Winding 3 CT Configuration
Unsigned Integer 16 Bits
0 = Wye
1 = Delta, IA-IC
2 = Delta, IA- IB
63593
Winding Phase Comp – Windings
1-3
Unsigned Integer 16 Bits
0<=Range <=330 / 30
Counters
TPU2000/TPU2000R has the ability to count breaker operations in a variety of modes. The same registers can
be accessed via a Modbus Code 03 (Read Holding Registers). For 4X read access, refer to Table 22. The same
information can be read via the refresh register capability through Register 61922. To reset the Breaker
Counters, write the value of 0 to Registers 61536 through 61547.
Table 5-74 is common to both the 2 Winding and 3 Winding TPU2000R and TPU2000 (available in 2 Winding
Format Only). Table 5-74 is only available for configuration of the TPU2000R 3 Winding Relay.
Table 5-74. Counter Register Assignment