TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
210
Register
Address
Item Description
63712 SPARE_1
63713 Execute
Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
Unsigned 16 Bits
63714
Access Password
ASCII – 2 Characters Leftmost Digits
63715
Access Password
ASCII – 2 Characters Rightmost Digits
63716 SPARE_2
63717
Through Fault Sum KSI Phase A –
Winding 3
Unsigned 16 Bit
0 – 9999
Kiloamps Symmetrical – Current existing
when breaker opened Phase A Winding 3
63718
Through Fault Sum KSI Phase B –
Winding 3
Unsigned 16 Bit
0 – 9999
Kiloamps Symmetrical – Current existing
when breaker opened Phase A Winding 3
63719
Through Fault Sum KSI Phase C –
Winding 3
Unsigned 16 Bit
0 – 9999
Kiloamps Symmetrical – Current existing
when breaker opened Phase A Winding 3
Alarm Settings
Counter and Metering settings may be set and configured via the registers from 61664 through 61682. Setting of
the quantities is relatively straightforward. It should be noted that Positive Watt Alarm 1 and Positive Watt Alarm 2
units are displayed in either KWhr or MWhr according to bit 6 of Configuration Flag in the Configuration Settings
Group. If bit is set to one, use MWhr, if bit is zero, use KWhr.
Table 5-75. Alarm Setting Table
Register
Address
Item Description
61664 SPARE_1
61665 Execute
Register
0 = No Action
1 = Update Registers
2 = Refresh Registers
Unsigned 16 Bits
61666
Access Password
ASCII – 2 Characters Leftmost Digits
61667
Access Password
ASCII – 2 Characters Rightmost Digits
61668 SPARE_2
61669
Through Faults
Unsigned Integer 16 Bits
0<=Range <=9999
61670
Through Fault Summation KSI
Alarm
Unsigned Integer 16 Bits
0<=Range <=9999
61671
Through Fault Summation
Cycles
Unsigned Integer 16 Bits
0<=Range <=9999
61672
Overcurrent Trip Alarms
Unsigned Integer 16 Bits
0<=Range <=9999
61673
Differential Trip Alarms
Unsigned Integer 16 Bits
0<=Range <=9999