TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
328
2/2
spare
2/3
C Subcommand = 0xbc
3/1
Through Faults Counter high byte (0-9999)
3/2
Through Faults Counter low byte
3/3
Thr Fault Sum kAmp A Counter high byte (0-9999)
4/1
Thr Fault Sum kAmp A Counter low byte
4/2
Through Fault Sum Cyc Counter high byte (0-99990)
4/3
Through Fault Sum Cyc Counter low byte
5/1
Overcurrent Trips Counter high byte (0-9999)
5/2
Overcurrent Trips Counter low byte
5/3
Differential Trips Counter high byte (0-9999)
6/1
Differential Trips Counter low byte
6/2
Thr Fault Sum kAmp B Counter high byte (0-9999)
6/3
Thr Fault Sum kAmp B Counter low byte
7/1
Thr Fault Sum kAmp C Counter high byte (0-9999)
7/2
Thr Fault Sum kAmp C Counter low byte
7/3
Spare
8/1
Spare
8/2
Checksum high byte
8/3
Checksum low byte
11.13 Receive Alarm Settings ( 3 11 13 )
Low byte consists of bits 0 through 7.
High byte consists of bits 8 through 15.
Msg byte Definition
1/1
Most significant high byte of password
1/2
Most significant low byte of password
1/3
Least significant high byte of password
2/1
Least significant low byte of password
2/2
spare
2/3
C Subcommand = 0xbd
3/1
Through Faults Alarm Threshold high byte (0-9999)
3/2
Through Faults Alarm Threshold low byte
3/2
Through Fault Sum kAmp Alarm Thres high (0-9999)
4/1
Through Fault Sum kAmp Alarm Threshold low byte
4/2
Through Fault Sum Cyc Alarm high (0-99990, /10)
4/3
Through Fault Sum Cyc Alarm Threshold low byte
5/1
Overcurrent Trips Alarm high byte (0-9999)
5/2
Overcurrent Trips Alarm low byte
5/3
Differential Trips Alarm high byte (0-9999)
6/1
Differential Trips Alarm low byte
6/2
Phase Demand Alarm high byte (1-9999)
6/3
Phase Demand Alarm low byte
7/1
Neutral Demand Alarm high byte (1-9999)
7/2
Neutral Demand Alarm low byte
7/3
Load Alarm high byte (1-9999)
8/1
Load Alarm low byte
8/2
Phase Demand Alarm high byte (1-9999,10000=Disables)
8/3
Phase Demand Alarm low byte
9/1
Low PF Alarm high byte(0.5-1.0 *100, 101=Disables)
9/2
Low PF Alarm low byte
9/3
High PF Alarm high byte(0.5-1.0 *100, 101=Disables)
10/1
High Pf Alarm low byte
10/2
Positive kVAR Alarm high byte (10-99990 / 10,10000=Disable)
10/3
Positive kVAR Alarm low byte
11/1
Negative kVAR Alarm high byte (10-99990 /10,10000=Disable)
11/2
Negative kVAR Alarm high byte