TPU2000/2000R Modbus/Modbus Plus Automation Guide
331
5/1
Coefficient B |
5/2
Coefficient B |
5/3
Coefficient B (low byte)
6/1
Coefficient C (high byte)
6/2
Coefficient C |
6/3
Coefficient C |
7/1
Coefficient C (low byte)
7/2
Coefficient P (high byte)
7/3
Coefficient P |
8/1
Coefficient P |
8/2
Coefficient P (low byte)
8/3
Spare
9/1
Spare
9/2
Checksum (high byte)
9/3
Checksum (low byte)
13.2 Receive First Overcurrent Curve Data Set ( 3 13 2 )
Data Byte Definition
1/1
Most significant high byte of password
1/2
Most significant low byte of password
1/3
Least significant high byte of password
2/1
Least significant low byte of password
2/2
Spare
2/3
C Subcommand = 0xd2
3/1
Programmable
curve
number
User Programmable Curve number: 1=User 1; 2=User 2; 3=User 3
3/2
Segment 0: Endrange (high byte)
3/3
Segment 0: Endrange (low byte)
4/1
Segment 0: Alpha (high byte)
4/2
Segment 0: Alpha |
4/3
Segment 0: Alpha |
5/1
Segment 0: Alpha (low byte)
5/2
Segment 0: Beta (high byte)
5/3
Segment 0: Beta |
6/1
Segment 0: Beta |
6/2
Segment 0: Beta (low byte)
6/3-9/3
Segment 1 (same as segment 0)
10/1-14/1
Segment 2 (same as segment 0)
14/2-18/2
Segment 3 (same as segment 0)
18/3-22/3
Segment 4 (same as segment 0)
23/1-27/1
Segment 5 (same as segment 0)
27/2-31/2
Segment 6 (same as segment 0)
31/3-35/3
Segment 7 (same as segment 0)
36/1
Spare
36/2
Checksum (high byte)
36/3
Checksum (low byte)
13.3 Receive Next Overcurrent Curve Data Set ( 3 13 3 )
Same format as ( 3 13 2 ).
13.4 Receive Overcurrent Curve Pointer Table ( 3 13 4 )
Data Byte Definition
1/1
Most significant high byte of password
1/2
Most significant low byte of password
1/3
Least significant high byte of password
2/1
Least significant low byte of password