The connection type for the main and the pilot fuse groups must be
consistent.
The settings
Vdif Main block
,
Vdif Pilot alarm
and
VSealIn
are in percentage of the
base voltage,
VBase
. Set
VBase
to the primary rated phase-to-phase voltage of the
potential voltage transformer.
VBase
is available in the Global Base Value groups; the
particular Global Base Value group, that is used by VDSPVC (60), is set by the setting
parameter
GlobalBaseSel
.
The settings
Vdif Main block
and
Vdif Pilot alarm
should be set low (approximately
30% of
VBase
) so that they are sensitive to the fault on the voltage measurement
circuit, since the voltage on both sides are equal in the healthy condition. If
V
SetPrim
is
the desired pick up primary phase-to-phase voltage of measured fuse group, the setting
of
Vdif Main block
and
Vdif Pilot alarm
will be given according to equation
Vdif Main block or Vdif Pilot alarm=
SetPrim
Base
V
V
⋅
100
ANSI13000279 V1 EN-US
(Equation 88)
V
SetPrim
is defined as phase to neutral or phase to phase voltage dependent of the
selected
ConTypeMain
and
ConTypePilot
. If
ConTypeMain
and
ConTypePilot
are set to
Ph-N
than the function performs internally the rescaling of
V
SetPrim
.
When
SealIn
is set to
On
and the fuse failure has last for more than 5 seconds, the
blocked protection functions will remain blocked until normal voltage conditions are
restored above the
VSealIn
setting. The fuse failure outputs are deactivated when the
normal voltage conditions are restored.
Section 11
1MRK 505 370-UUS A
Secondary system supervision
292
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...