minimize any risk for unwanted operation of the busbar differential protection zones
due to late inclusion of respective bay current into the differential measuring circuit.
18.1.3
Setting guidelines
M12454-3 v6
64 kbit and 2 Mbit mode common settings
ChannelMode
defines how an IED discards the LDCM information when one of the
IEDs in the system is out of service: it can either be done on the IED out of service by
setting all local LDCMs to channel mode
OutOfService
or at the remote end by setting
the corresponding LDCM to channel mode
Blocked
. If
OutOfService
is selected, the
IED should have active communication to the remote end during the whole
maintenance process, that is, no restart or removal of the fibre can be done.
This setting does not apply to two-end communication.
Blocked
IED does not use data from the LDCM
OutOfService
IED informs the remote end that it is out of service
TerminalNo
is used to assign a unique address to each LDCM in all current differential
IEDs. Up to 256 LDCMs can be assigned a unique number. For example, in a local
IED with two LDCMs:
•
LDCM for slot 305: set
TerminalNo
to 1 and
RemoteTermNo
to 2
•
LDCM for slot 306: set
TerminalNo
to 3 and
RemoteTermNo
to 4
In multiterminal current differential applications,with 4 LDCMs in each IED, up to 20
unique addresses must be set.
A unique address is necessary to give high security against incorrect
addressing in the communication system. If the same number is used
for
TerminalNo
in some of the LDCMs, a loop-back test in the
communication system can give an incorrect trip.
RemoteTermNo
is used to assign a number to each related LDCM in the remote IED.
For each LDCM,
RemoteTermNo
is set to a different value than
TerminalNo
, but equal
to the
TerminalNo
of the remote end LDCM. In the remote IED,
TerminalNo
and
RemoteTermNo
are reversed as follows:
•
LDCM for slot 305: set
TerminalNo
to 2 and
RemoteTermNo
to 1
•
LDCM for slot 306: set
TerminalNo
to 4 and
RemoteTermNo
to 3
1MRK 505 370-UUS A
Section 18
Remote communication
Busbar protection REB670 2.2 ANSI
495
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...