Section 21
Requirements
21.1
Current transformer requirements
IP15171-1 v2
M11609-3 v2
The performance of a protection function will depend on the quality of the measured
current signal. Saturation of the current transformers (CTs) will cause distortion of the
current signals and can result in a failure to operate or cause unwanted operations of
some functions. Consequently CT saturation can have an influence on both the
dependability and the security of the protection. This protection IED has been designed
to permit heavy CT saturation with maintained correct operation.
21.1.1
Current transformer basic classification and requirements
M11611-3 v2
M11611-4 v5
To guarantee correct operation, the current transformers (CTs) must be able to correctly
reproduce the current for a minimum time before the CT will begin to saturate. To
fulfill the requirement on a specified time to saturation the CTs must fulfill the
requirements of a minimum secondary e.m.f. that is specified below.
CTs are specified according to many different classes and standards. In principle, there
are three different types of protection CTs. These types are related to the design of the
iron core and the presence of airgaps. Airgaps affects the properties of the remanent
flux.
The following three different types of protection CTs have been specified:
•
The High Remanence type with closed iron core and no specified limit of the
remanent flux
•
The Low Remanence type with small airgaps in the iron core and the remanent
flux limit is specified to be maximum 10% of the saturation flux
•
The Non Remanence type with big airgaps in the iron core and the remanent flux
can be neglected
Even though no limit of the remanent flux is specified in the IEC standard for closed
core CTs, it is a common opinion that the remanent flux is normally limited to
maximum 75 - 80 % of the saturation flux.
Since approximately year 2000 some CT manufactures have introduced new core
materials that gradually have increased the possible maximum levels of remanent flux
even up to 95 % related to the hysteresis curve. Corresponding level of actual remanent
1MRK 505 370-UUS A
Section 21
Requirements
Busbar protection REB670 2.2 ANSI
523
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...