12.4.2.4
Configuration setting
M13560-108 v4
If there is no bypass busbar and therefore no 789 disconnector, then the interlocking for
789 is not used. The states for 789, 7189G, BB7_D, BC_17, BC_27 are set to open by
setting the appropriate module inputs as follows. In the functional block diagram, 0 and
1 are designated 0=FALSE and 1=TRUE:
•
789_OP = 1
•
789_CL = 0
•
7189G_OP = 1
•
7189G_CL = 0
•
BB7_D_OP = 1
•
BC_17_OP = 1
•
BC_17_CL = 0
•
BC_27_OP = 1
•
BC_27_CL = 0
•
EXDU_BPB = 1
•
VP_BB7_D = 1
•
VP_BC_17 = 1
•
VP_BC_27 = 1
If there is no second busbar WA2 and therefore no 289 disconnector, then the
interlocking for 289 is not used. The state for 289, 2189G, BC_12, BC_27 are set to
open by setting the appropriate module inputs as follows. In the functional block
diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
•
289_OP = 1
•
289_CL = 0
•
2189G_OP = 1
•
2189G_CL = 0
•
BC_12_CL = 0
•
BC_27_OP = 1
•
BC_27_CL = 0
•
VP_BC_12 = 1
Section 12
1MRK 505 370-UUS A
Control
368
Busbar protection REB670 2.2 ANSI
Application manual