Ix>
: Operation phase current level for step x given in % of
IBase
.
tx:
Definite time delay for step x. Used if definite time characteristic is chosen. Setting
range: 0.000-60.000 s in step of 0.001 s. Note that the value set is the time between
activation of the start and the trip outputs.
kx
: Time multiplier for the dependent (inverse) characteristic.
InxMult
: Multiplier for scaling of the current setting value. If a binary input signal
(enableMultiplier) is activated the current operation level is increase by this setting
constant. Setting range: 1.0-10.0
txMin
: Minimum operation time for IEC inverse time characteristics. At high currents
the inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step can never be shorter than the setting. Setting
range: 0.000-60.000 s in step of 0.001 s.
ResetTypeCrvx
: The reset of the delay timer can be made in different ways. By
choosing setting the possibilities are according to table
.
Table 29:
Reset possibilities
Curve name
Curve index no.
Instantaneous
1
IEC Reset (constant time)
2
ANSI Reset (inverse time)
3
The delay characteristics are described in the “
Technical reference manual
”. There are
some restrictions regarding the choice of reset delay.
For the independent time delay characteristics the possible delay time settings are
instantaneous (1) and IEC (2 = set constant time reset).
For ANSI inverse time delay characteristics all three types of reset time characteristics
are available; instantaneous (1), IEC (2 = set constant time reset) and ANSI (3 =
current dependent reset time).
For IEC inverse time delay characteristics the possible delay time settings are
instantaneous (1) and IEC (2 = set constant time reset).
For the customer tailor made inverse time delay characteristics (type 17) all three types
of reset time characteristics are available; instantaneous (1), IEC (2 = set constant time
reset) and ANSI (3 = current dependent reset time). If the current dependent type is
used then settings pr, tr and cr must be given.
Section 7
1MRK 505 370-UUS A
Current protection
190
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...