
A permanent fault will cause the line protection to trip again when it recloses in an
attempt to energize the line.
The auto reclosing function allows a number of parameters to be adjusted.
Examples:
•
number of auto reclosing shots
•
auto reclosing program
•
auto reclosing dead times for each shot
12.2.2.1
Auto reclosing operation Off and On
M12391-91 v6
Operation of the automatic recloser can be set to Off and On by a setting parameter or
by external control. The setting parameter
Operation
=
Disabled
, or
Enabled
sets the
function to Off or On. With the settings
Operation
=
Enabled
and
ExternalCtrl
=
Enabled
, the control is made by input signal pulses to the inputs On and Off, for
example, from a control system or by a control switch.
When the auto recloser is set On, the
SETON
output is set, and the auto recloser
becomes operative if other conditions such as circuit breaker is closed and circuit
breaker is ready are also fulfilled, the
READY
output is activated (high). Then the auto
recloser is ready to accept a start.
12.2.2.2
Initiate auto reclosing and conditions for start of a reclosing cycle
M12391-94 v5
The usual way to start an auto reclosing cycle, or sequence, is to start it at selective
tripping by line protection by applying a signal to the
RI
input. Starting signals can be
either, general trip signals or, only the conditions for differential, distance protection
zone 1 and distance protection aided trip. In some cases also directional ground fault
protection aided trip can be connected to start an auto reclose attempt. If general trip is
used to start the auto recloser it is important to block it from other functions that should
not start an auto reclosing sequence.
In cases where one wants to differentiate three-phase auto reclosing dead time, for
different power system configuration or at tripping by different protection stages, one
can also use the
RI_HS
input (initiate high-speed reclosing). When initiating
RI_HS
,
the auto reclosing dead time for three-phase shot 1,
t1 3PhHS
is used and the closing is
done without checking the synchrocheck condition.
A number of conditions need to be fulfilled for the start to be accepted and a new auto
reclosing cycle to be started. They are linked to dedicated inputs. The inputs are:
Section 12
1MRK 505 370-UUS A
Control
318
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...