19
Menu
20
Clear
21
Help
22
Communication port
23
Programmable indication LEDs
24
IED status LEDs
5.4
Local HMI functionality
5.4.1
Protection and alarm indication
GUID-09CCB9F1-9B27-4C12-B253-FBE95EA537F5 v15
Protection indicators
The protection indicator LEDs are Normal, Pickup and Trip.
Table 9:
Normal LED (green)
LED state
Description
Off
Auxiliary supply voltage is disconnected.
On
Normal operation.
Flashing
Internal fault has occurred.
Table 10:
PickUp LED (yellow)
LED state
Description
Off
Normal operation.
On
A protection function has picked up and an indication message is displayed.
The pick up indication is latching and must be reset via communication,
LHMI or binary input on the LEDGEN component. To open the reset menu
on the LHMI, press
.
Flashing
The IED is in test mode and protection functions are blocked, or the
IEC61850 protocol is blocking one or more functions.
The indication disappears when the IED is no longer in test mode and
blocking is removed. The blocking of functions through the IEC61850
protocol can be reset in Main menu/Test/Reset IEC61850 Mod. The yellow
LED changes to either On or Off state depending on the state of operation.
Section 5
1MRK 505 370-UUS A
Local HMI
104
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...