Mode
: The voltage and current used for the power measurement. The setting
possibilities are shown in table
.
Table 34:
Complex power calculation
Set value
Mode
Formula used for complex power calculation
A,B,C
*
*
*
A
B
C
A
B
C
S V
I
V
I
V
I
=
×
+
×
+
×
EQUATION2038 V1 EN-US
(Equation 55)
Arone
*
*
A
C
AB
BC
S V
I
V
I
=
×
×
-
EQUATION2039 V1 EN-US
(Equation 56)
PosSeq
*
PosSeq
PosSeq
S 3 V
I
= ×
×
EQUATION2040 V1 EN-US
(Equation 57)
A,B
*
A
B
AB
*
S
V
(I
I
)
=
×
-
EQUATION2041 V1 EN-US
(Equation 58)
B,C
*
B
C
BC
*
S
V
(I
I
)
=
×
-
EQUATION2042 V1 EN-US
(Equation 59)
C,A
*
C
A
CA
*
S
V
(I
I
)
=
×
-
EQUATION2043 V1 EN-US
(Equation 60)
A
*
A
A
S 3 V
I
= ×
×
EQUATION2044 V1 EN-US
(Equation 61)
B
*
B
B
S 3 V
I
= ×
×
EQUATION2045 V1 EN-US
(Equation 62)
C
*
C
C
S 3 V
I
= ×
×
EQUATION2046 V1 EN-US
(Equation 63)
The function has two stages that can be set independently.
With the parameter
OpMode1(2)
the function can be set
Enabled
/
Disabled
.
The function gives trip if the power component in the direction defined by the setting
Angle1(2)
is larger than the set pick up power value
Power1(2)
1MRK 505 370-UUS A
Section 7
Current protection
Busbar protection REB670 2.2 ANSI
231
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...