11.1.3.5
Delta V and delta I
GUID-02336F26-98C0-419D-8759-45F5F12580DE v7
Set the operation mode selector
OpDVDI
to
Enabled
if the delta function shall be in
operation.
The setting of
DVPU
should be set high (approximately 60% of
VBase
) and the current
threshold
DIPU
low (approximately 10% of
IBase
) to avoid unwanted operation due to
normal switching conditions in the network. The delta current and delta voltage
function shall always be used together with either the negative or zero sequence
algorithm. If
VSet
prim
is the primary voltage for operation of dU/dt and
ISet
prim
the
primary current for operation of dI/dt, the setting of
DVPU
and
DIPU
will be given
.
DVPU
VSet
VBase
prim
=
⋅
100
EQUATION1765-ANSI V2 EN-US
(Equation 86)
DIPU
ISet
IBase
prim
=
⋅
100
ANSIEQUATION2385 V2 EN-US
(Equation 87)
The voltage thresholds
VPPU
is used to identify low voltage condition in the system.
Set
VPPU
below the minimum operating voltage that might occur during emergency
conditions. A setting of approximately 70% of
VBase
is recommended.
The current threshold
50P
shall be set lower than the
IMinOp
for the distance
protection function. A 5...10% lower value is recommended.
11.1.3.6
Dead line detection
M13683-78 v4
The condition for operation of the dead line detection is set by the parameters
IDLDPU
for the current threshold and
UDLD<
for the voltage threshold.
Set the
IDLDPU
with a sufficient margin below the minimum expected load current. A
safety margin of at least 15-20% is recommended. The operate value must however
exceed the maximum charging current of an overhead line, when only one phase is
disconnected (mutual coupling to the other phases).
Set the
VDLDPU
with a sufficient margin below the minimum expected operating
voltage. A safety margin of at least 15% is recommended.
11.2
Fuse failure supervision VDSPVC (60)
GUID-9C5BA1A7-DF2F-49D4-A13A-C6B483DDFCDC v2
1MRK 505 370-UUS A
Section 11
Secondary system supervision
Busbar protection REB670 2.2 ANSI
289
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...