•
989_OP = 1
•
989_CL = 0
•
989G_OP = 1
•
989G_CL = 0
If, in this case, line voltage supervision is added, then rather than setting 989 to open
state, specify the state of the voltage supervision:
•
989_OP = VOLT_OFF
•
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
•
VOLT_OFF = 1
•
VOLT_ON = 0
12.4.9
Interlocking for breaker-and-a-half diameter BH (3)
IP14173-1 v3
12.4.9.1
Application
M13570-3 v6
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half
diameter according to figure
.
Section 12
1MRK 505 370-UUS A
Control
396
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...