The following settings can be done for the four step phase overcurrent protection.
Operation
:
Off/On
IBase
: Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the protected
object.
2ndHarmStab
: Operate level of 2
nd
harmonic current restrain set in % of the
fundamental current. The setting range is 5-100% of IBase in steps of 1%. Default
setting is 20%.
HarmRestrainx
:
Disabled/Enabled
, enables blocking from harmonic restrain.
7.2.3.1
Settings for each step (x = 1-4)
SEMOD127941-18 v4
Characteristx
: Selection of time delay characteristic for step x. Definite time delay and
different types of inverse time delay characteristics are available according to table
.
Table 28:
Inverse time delay characteristics
Curve name
ANSI Extremely Inverse
ANSI Very Inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI/IEEE Definite time
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
IEC Normal Inverse
IEC Very Inverse
IEC Inverse
IEC Extremely Inverse
IEC Short Time Inverse
IEC Long Time Inverse
IEC Definite Time
User Programmable
ASEA RI
RXIDG (logarithmic)
The different characteristics are described in the “
Technical reference manual
”.
1MRK 505 370-UUS A
Section 7
Current protection
Busbar protection REB670 2.2 ANSI
189
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...