Figure 57:
Example of H-type station
The requirement for the busbar protection scheme for this type of station may differ
from utility to utility. It is possible to apply just one overall differential zone, which
protects both busbar sections. However, at an internal fault on any of the two buses all
feeder circuit breakers have to be tripped, which will cause loss of supply to all loads
connected to this station. Some utilities prefer to have two differential zones, one for
each bus section.
The most common setups for this type of station are given in the following table.
Section 6
1MRK 505 370-UUS A
Differential protection
140
Busbar protection REB670 2.2 ANSI
Application manual