8.1.2.2
Disconnected equipment detection
M13851-53 v3
The setting must be below the lowest occurring "normal" voltage and above the highest
occurring voltage, caused by inductive or capacitive coupling, when the equipment is
disconnected.
8.1.2.3
Power supply quality
M13851-56 v3
The setting must be below the lowest occurring "normal" voltage and above the lowest
acceptable voltage, due to regulation, good practice or other agreements.
8.1.2.4
Voltage instability mitigation
M13851-59 v3
This setting is very much dependent on the power system characteristics, and thorough
studies have to be made to find the suitable levels.
8.1.2.5
Backup protection for power system faults
M13851-62 v3
The setting must be below the lowest occurring "normal" voltage and above the highest
occurring voltage during the fault conditions under consideration.
8.1.2.6
Settings for two step undervoltage protection
M13851-65 v14
The following settings can be done for Two step undervoltage protection UV2PTUV
(27):
ConnType
: Sets whether the measurement shall be phase-to-ground fundamental value,
phase-to-phase fundamental value, phase-to-ground RMS value or phase-to-phase
RMS value.
Operation
:
Disabled
or
Enabled
.
VBase
(given in
GlobalBaseSel
): Base voltage phase-to-phase in primary kV. This
voltage is used as reference for voltage setting. UV2PTUV (27) will operate if the
voltage becomes lower than the set percentage of
VBase
. This setting is used when
ConnType
is set to
PhPh DFT
or
PhPh RMS
. Therefore, always set
VBase
as rated
primary phase-to-phase voltage of the protected object. For more information, refer to
the
Technical manual
.
The setting parameters described below are identical for the two steps (
n
= 1 or 2).
Therefore, the setting parameters are described only once.
Characteristicn
: This parameter gives the type of time delay to be used. The setting
can be
Definite time
,
Inverse Curve A
,
Inverse Curve B
,
Prog. inv. curve
. The selection
is dependent on the protection application.
Section 8
1MRK 505 370-UUS A
Voltage protection
244
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...