The different characteristics are described in the Technical Reference Manual (TRM).
Pickupx
: Operation negative sequence current level for step x given in % of
IBase
.
tx
: Definite time delay for step
x
. The definite time
tx
is added to the inverse time when
inverse time characteristic is selected. Note that the value set is the time between
activation of the start and the trip outputs.
TDx
: Time multiplier for the dependent (inverse) characteristic.
IMinx
: Minimum pickup current for step x in % of
IBase
. Set
IMinx
below
Pickupx
for
every step to achieve ANSI reset characteristic according to standard. If
IMinx
is set
above
Pickupx
for any step the ANSI reset works as if current is zero when current
drops below
IMinx
.
MultPUx
: Multiplier for scaling of the current setting value. If a binary input signal
(ENMULTx) is activated the current operation level is multiplied by this setting
constant.
txMin
: Minimum operation time for inverse time characteristics. At high currents the
inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step can never be shorter than the setting.
IMinx
Operate time
Current
tx
txMin
IEC10000058
IEC10000058 V2 EN-US
Figure 98:
Minimum operate current and operation time for inverse time
characteristics
ResetTypeCrvx
: The reset of the delay timer can be made in different ways. By
choosing setting there are the following possibilities:
Section 7
1MRK 505 370-UUS A
Current protection
208
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...