17.3
LON communication protocol
IP14420-1 v1
17.3.1
Application
IP14863-1 v1
M14804-3 v5
Control Center
IED
IED
IED
Gateway
Star coupler
RER 111
Station HSI
MicroSCADA
IEC05000663-1-en.vsd
IEC05000663 V2 EN-US
Figure 204:
Example of LON communication structure for a substation automation
system
An optical network can be used within the substation automation system. This enables
communication with the IEDs through the LON bus from the operator’s workplace,
from the control center and also from other IEDs via bay-to-bay horizontal
communication. For LON communication an SLM card should be ordered for the
IEDs.
The fibre optic LON bus is implemented using either glass core or plastic core fibre
optic cables.
Table 51:
Specification of the fibre optic connectors
Glass fibre
Plastic fibre
Cable connector
ST-connector
snap-in connector
Cable diameter
62.5/125 m
1 mm
Max. cable length
1000 m
10 m
Table continues on next page
Section 17
1MRK 505 370-UUS A
Station communication
478
Busbar protection REB670 2.2 ANSI
Application manual