17.5
IEC 60870-5-103 communication protocol
IP14615-1 v2
17.5.1
Application
IP14864-1 v1
M17109-3 v6
TCP/IP
Control
Center
IED
IED
IED
Gateway
Star coupler
Station
HSI
ANSI05000660-4-en.vsd
ANSI05000660 V4 EN-US
Figure 206:
Example of IEC 60870-5-103 communication structure for a substation
automation system
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must have
software that can interpret the IEC 60870-5-103 communication messages.
When communicating locally in the station using a Personal Computer (PC) or a
Remote Terminal Unit (RTU) connected to the Communication and processing
module, the only hardware needed is optical fibres and an opto/electrical converter for
the PC/RTU, or a RS-485 connection depending on the used IED communication
interface.
17.5.1.1
Functionality
M17109-38 v3
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system. In IEC terminology a
primary station is a master and a secondary station is a slave. The communication is
based on a point-to-point principle. The master must have software that can interpret
1MRK 505 370-UUS A
Section 17
Station communication
Busbar protection REB670 2.2 ANSI
483
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...