The same type of module (A1A2_DC) is used for different busbars, that is, for both
bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding
signals from busbar B are used.
en04000498_ansi.vsd
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
DB_BUS DB_BUS
DB_BUS DB_BUS
(WA1)A1
(WA2)B1
B2
A2
ANSI04000498 V1 EN-US
Figure 163:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
S1DC_OP
All disconnectors on bus-section 1 are open.
S2DC_OP
All disconnectors on bus-section 2 are open.
VPS1_DC
The switch status of all disconnectors on bus-section 1 is valid.
VPS2_DC
The switch status of all disconnectors on bus-section 2 is valid.
EXDU_BB
No transmission error from double-breaker bay (DB) that contains the above
information.
These signals from each double-breaker bay (DB_BUS) are needed:
Signal
189OPTR
189 is open.
289OPTR
289 is open.
VP189TR
The switch status of 189 is valid.
VP289TR
The switch status of 289 is valid.
EXDU_DB
No transmission error from the bay that contains the above information.
The logic is identical to the double busbar configuration “Signals in single breaker
arrangement”.
For a bus-section disconnector, these conditions from the A1 busbar section are valid:
1MRK 505 370-UUS A
Section 12
Control
Busbar protection REB670 2.2 ANSI
385
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...