depends on the status of the six busbar disconnectors (i.e. three on each side). More
specifically, the following need to be done, for each bus coupler bay:
1. Connect the two auxiliary contacts (i.e. normally open and normally closed
auxiliary contacts or also sometimes called “a & b contacts”) from each of the six
busbar disconnectors to the IED. This can be done by wiring using binary inputs
or via communication (e.g. via GOOSE or via LDCM).
2. Use six BDCGAPC function blocks (i.e. one per busbar disconnector) to derive
open or closed status of the respective disconnector primary contacts.
3. Connect the close status output from each BDCGAPC function block to the
respective zone control input on the bus-interconnector function block
BICPTRC_xx. This will ensure proper dynamic inclusion of the CT measurements
from the two CTs located within the bus-section bay towards the differential
protection zones.
4. Connect the two currents from the TRM via pre-processing blocks to the bus-
interconnector function block BICPTRC_xx. Ensure overlapping of the two CTs.
In case that only one CT is available, connect this CT to both CT inputs on the
BICPTRC_xx function block and then invert one of the two inputs in software by
using the parameter setting
OperMode
. This shall be done taking into account the
actual location of the CT star point in this bay.
5. Connect the trip output from BICPTRC_xx function block to the binary output
contact (alternatively the tripping can also be arranged using GOOSE
communication). This will ensure proper tripping of the bus-coupler bay for any
relevant operation of the BBP including BFP tripping.
ACT configuration example for Bus-coupler 01 located at Section 1 is given in Figure
. Any other bus coupler bays located at Section 1 shall be engineered in the similar
way. For the bus coupler bays located at Section 2, similar steps to Step 3 shall be
done, except the relevant zones are then Z4, Z5 and Z6.
Section 6
1MRK 505 370-UUS A
Differential protection
160
Busbar protection REB670 2.2 ANSI
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...