The time parameter
tResResponse
is the allowed time from reservation request to the
feedback reservation granted from all bays involved in the reservation function. When
the time has expired, the control function is reset, and a cause-code is given.
tSynchrocheck
is the allowed time for the synchronism check function to fulfill the
close conditions. When the time has expired, the function tries to start the
synchronizing function. If
tSynchrocheck
is set to
0
, no synchrocheck is done, before
starting the synchronizing function.
The timer
tSynchronizing
supervises that the signal synchronizing in progress is
obtained in SCSWI after start of the synchronizing function. The start signal for the
synchronizing is set if the synchronism check conditions are not fulfilled. When the
time has expired, the control function is reset, and a cause-code is given. If no
synchronizing function is included, the time is set to
0
, which means no start of the
synchronizing function is done, and when
tSynchrocheck
has expired, the control
function is reset and a cause-code is given.
tExecutionFB
is the maximum time between the execute command signal and the
command termination. When the time has expired, the control function is reset and a
cause-code is given.
tPoleDiscord
is the allowed time to have discrepancy between the poles at control of
three single-phase breakers. At discrepancy an output signal is activated to be used for
trip or alarm, and during a command, the control function is reset, and a cause-code is
given.
SuppressMidPos
when
On
suppresses the mid-position during the time
tIntermediate
of
the connected switches.
The parameter
InterlockCheck
decides if interlock check should be done at both select
and operate, Sel & Op phase, or only at operate, Op phase.
12.3.3.3
Switch (SXCBR/SXSWI)
M16675-3 v8
tStartMove
is the supervision time for the apparatus to start moving after a command
execution is done from the SCSWI function. When the time has expired, the command
supervision is reset, and a cause-code is given.
During the
tIntermediate
time, the position indication is allowed to be in an
intermediate (00) state. When the time has expired, the command supervision is reset,
and a cause-code is given. The indication of the mid-position at SCSWI is suppressed
during this time period when the position changes from open to close or vice-versa if
the parameter
SuppressMidPos
is set to
On
in the SCSWI function.
If the parameter
AdaptivePulse
is set to
Adaptive
the command output pulse resets
when a new correct end position is reached. If the parameter is set to
Not adaptive
the
1MRK 505 370-UUS A
Section 12
Control
Busbar protection REB670 2.2 ANSI
359
Application manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 40: ...34 ...
Страница 72: ...66 ...
Страница 102: ...96 ...
Страница 266: ...260 ...
Страница 272: ...266 ...
Страница 290: ...284 ...
Страница 432: ...426 ...
Страница 542: ...536 ...
Страница 552: ...546 ...
Страница 553: ...547 ...