V0I0 OR V2I2
; Both negative and zero sequence is activated and working in
parallel in an OR-condition
•
V0I0 AND V2I2
; Both negative and zero sequence is activated and working in
series (AND-condition for operation)
•
OptimZsNs
; Optimum of negative and zero sequence (the function that has the
highest magnitude of measured negative and zero sequence current will be activated)
The delta function can be activated by setting the parameter
OpDVDI
to
Enabled
.
When selected it operates in parallel with the sequence based algorithms.
As soon as any fuse failure situation is detected, signals FuseFailDetZeroSeq,
FuseFailDetNegSeq or FuseFailDetDVDI, and the specific functionality is released,
the function will activate the output signal BLKV. The output signal BLKZ will be
activated as well if not the internal dead phase detection, DeadLineDet1Ph, is not
activated at the same time. The output BLKV can be used for blocking voltage related
measuring functions (under voltage protection, synchro-check, and so on). For
blocking of impedance protection functions output BLKZ shall be used.
If the fuse failure situation is present for more than 5 seconds and the setting parameter
SealIn
is set to
Enabled
it will be sealed in as long as at least one phase voltages is
below the set value
VSealInPU
. This will keep the BLKV and BLKZ signals activated
as long as any phase voltage is below the set value
VSealInPU
. If all three phase
voltages drop below the set value
VSealInPU
and the setting parameter
SealIn
is set to
Enabled
the output signal 3PH will also be activated. The signals 3PH, BLKV and
BLKZ signals will now be active as long as any phase voltage is below the set value
VSealInPU
.
If
SealIn
is set to
Enabled
the fuse failure condition is stored in the non volatile
memory in the IED. At start-up of the IED (due to auxiliary power interruption or re-
start due to configuration change) it checks the stored value in its non volatile memory
and re-establishes the conditions that were present before the shut down. All phase
voltages must be greater than
VSealInPU
before fuse failure is de-activated and
removes the block of different protection functions.
The output signal BLKV will also be active if all phase voltages have been above the
setting
VSealInPU
for more than 60 seconds, the zero or negative sequence voltage has
been above the set value
3V0PU
and
3V2PU
for more than 5 seconds, all phase
currents are below the setting
IDLDPU
(operate level for dead line detection) and the
circuit breaker is closed (input 52a is activated).
If a MCB is used then the input signal MCBOP is to be connected via a terminal binary
input to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKV and BLKZ in
order to block all the voltage related functions when the MCB is open independent of
the setting of
OpModeSel
or
OpDVDI
. An additional drop-out timer of 150 ms
Section 11
1MRK505222-UUS C
Secondary system supervision
608
Technical reference manual
Содержание Relion 670 series
Страница 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Страница 2: ......
Страница 40: ...34...
Страница 50: ...44...
Страница 60: ...54...
Страница 126: ...120...
Страница 384: ...378...
Страница 496: ...490...
Страница 556: ...550...
Страница 602: ...596...
Страница 620: ...614...
Страница 794: ...788...
Страница 864: ...858...
Страница 988: ...982...
Страница 998: ...992...
Страница 1084: ...1078...
Страница 1164: ...1158...
Страница 1168: ...1162...
Страница 1170: ...1MRK002802 AB 1 670 1 2 PG ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1164 Technical reference manual...
Страница 1171: ...1MRK002802 AB 2 670 1 2 PG ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1165 Technical reference manual...
Страница 1172: ...1MRK002802 AB 3 670 1 2 PG ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1166 Technical reference manual...
Страница 1173: ...1MRK002802 AB 4 670 1 2 PG ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1167 Technical reference manual...
Страница 1174: ...1MRK002802 AB 5 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1168 Technical reference manual...
Страница 1175: ...1MRK002802 AB 6 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1169 Technical reference manual...
Страница 1176: ...1MRK002802 AB 7 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1170 Technical reference manual...
Страница 1177: ...1MRK002802 AB 8 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1171 Technical reference manual...
Страница 1178: ...1MRK002802 AB 9 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1172 Technical reference manual...
Страница 1179: ...1MRK002802 AB 10 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1173 Technical reference manual...
Страница 1180: ...1MRK002802 AB 11 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1174 Technical reference manual...
Страница 1181: ...1MRK002802 AB 12 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1175 Technical reference manual...
Страница 1182: ...1MRK002802 AB 13 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1176 Technical reference manual...
Страница 1183: ...1MRK002802 AB 14 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1177 Technical reference manual...
Страница 1184: ...1MRK002802 AB 15 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1178 Technical reference manual...
Страница 1220: ...1214...
Страница 1230: ...1224...
Страница 1231: ...1225...