Table 290:
SAPTOF (81) Output signals
Name
Type
Description
TRIP
BOOLEAN
Operate/trip signal for frequency.
PICKUP
BOOLEAN
Start/pick-up signal for frequency.
BLKDMAGN
BOOLEAN
Blocking indication due to low magnitude.
FREQ
REAL
Measured frequency
9.2.5
Setting parameters
Table 291:
SAPTOF (81) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
VBase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
PUFrequency
35.00 - 75.00
Hz
0.01
51.20
Frequency setting pickup value.
IntBlockLevel
0 - 100
%VB
1
50
Internal blocking level in % of VBase.
TimeDlyOperate
0.000 - 60.000
s
0.001
0.000
Operate time delay in over/under-frequency
mode.
TimeDlyReset
0.000 - 60.000
s
0.001
0.000
Time delay for reset.
9.2.6
Technical data
Table 292:
SAPTOF (81) technical data
Function
Range or value
Accuracy
Operate value, pickup function
(35.00-75.00) Hz
± 2.0 mHz at
symmetrical three-
phase voltage
Operate time, pickup function
100 ms typically at f
set
-0.5 Hz to f
set
+0.5 Hz
-
Reset time, pickup function
100 ms typically
-
Operate time, definite time
function
(0.000-60.000)s
± 0.5% ± 10 ms
Reset time, definite time function
(0.000-60.000)s
± 0.5% ± 10 ms
9.3
Rate-of-change frequency protection SAPFRC (81)
1MRK505222-UUS C
Section 9
Frequency protection
561
Technical reference manual
Содержание Relion 670 series
Страница 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Страница 2: ......
Страница 40: ...34...
Страница 50: ...44...
Страница 60: ...54...
Страница 126: ...120...
Страница 384: ...378...
Страница 496: ...490...
Страница 556: ...550...
Страница 602: ...596...
Страница 620: ...614...
Страница 794: ...788...
Страница 864: ...858...
Страница 988: ...982...
Страница 998: ...992...
Страница 1084: ...1078...
Страница 1164: ...1158...
Страница 1168: ...1162...
Страница 1170: ...1MRK002802 AB 1 670 1 2 PG ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1164 Technical reference manual...
Страница 1171: ...1MRK002802 AB 2 670 1 2 PG ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1165 Technical reference manual...
Страница 1172: ...1MRK002802 AB 3 670 1 2 PG ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1166 Technical reference manual...
Страница 1173: ...1MRK002802 AB 4 670 1 2 PG ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1167 Technical reference manual...
Страница 1174: ...1MRK002802 AB 5 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1168 Technical reference manual...
Страница 1175: ...1MRK002802 AB 6 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1169 Technical reference manual...
Страница 1176: ...1MRK002802 AB 7 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1170 Technical reference manual...
Страница 1177: ...1MRK002802 AB 8 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1171 Technical reference manual...
Страница 1178: ...1MRK002802 AB 9 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1172 Technical reference manual...
Страница 1179: ...1MRK002802 AB 10 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1173 Technical reference manual...
Страница 1180: ...1MRK002802 AB 11 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1174 Technical reference manual...
Страница 1181: ...1MRK002802 AB 12 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1175 Technical reference manual...
Страница 1182: ...1MRK002802 AB 13 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1176 Technical reference manual...
Страница 1183: ...1MRK002802 AB 14 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1177 Technical reference manual...
Страница 1184: ...1MRK002802 AB 15 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1178 Technical reference manual...
Страница 1220: ...1214...
Страница 1230: ...1224...
Страница 1231: ...1225...