ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
73
The following parameters appear at
switching ON and OFF delay
:
Explanations relating to the on and off delay can be found under
, page 218. You will also find a timing diagram as well as
explanations on the effect of various ON and OFF telegrams in combination
with the
switching ON and OFF delay
.
Switching ON delay
in s [0…65,535]
Options: 0…5…65,535
Here you set the time by which an ON command is delayed after switch on.
Switching OFF delay
in s [0…65,535]
Options: 0…5…65,535
Here you set the time by which switch OFF is delayed after a switch OFF
command.
Value object "function time disable"
on bus voltage recovery
Options: unchanged
1, i.e., function time disable
0, i.e., function time enable
This parameter defines how the time function parameter should behave after
bus voltage recovery. With a telegram to the communication object
Disable
function time
the function time can be disabled or enabled.
•
unchanged:
After bus voltage recovery the function time reacts in the
same way as before bus voltage failure.
•
1, i.e., function time disable:
The function time is disabled by a telegram
with the value 1.
•
0, i.e., function time enable:
The function time is enabled by a telegram
with the value 0.