ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
141
3.2.7
Parameter window
Control input
In this parameter window all settings for the
Control input
are undertaken.
HVAC-System
Options:
1 Control value/4 pipe, with switching object.
2 Control values/2 pipe, with switching object
This parameter defines the pipe system which is used with the Room
Master.
The individual functions are described in the following chapters.
Important
If a valve is deactivated due to a conversion of the HVAC system,
the valve will be fully closed. A correction curve which may be set
will be ignored!
Monitoring control values
e.g.
thermostat
Options: no
yes
•
yes:
The communication object
Fault control value
is enabled.
Hereby for example, a thermostat can be cyclically monitored.
Note
During a fault (emergency operation) when the control signal from the
thermostat is no longer received, the Room Master autonomously
performs a
Pulse width modulation – calculation
, page 257, (
, page 255) For this purpose the Room Master uses
the programmable PWM cycle time.